Download Print this page

Simplex 4010ES Manual page 6

Hide thumbs Also See for 4010ES:

Advertisement

Master Controller (CPU)
The 4010ES Master Controller includes dedicated
2GB compact flash Mass Storage memory for on-site
system information storage and convenient Ethernet
service port access
Convenient front panel accessed Ethernet port for
quick and easy download of site-specific
programming
AND, firmware enhancements are made via software
downloads to the on-board flash memory
Every downloaded job is automatically stored to
Compact flash without overwriting earlier versions
providing a means for recovering previous
configurations
Downtime is reduced because the system stays
running during download
Modifications can be uploaded as well as
downloaded for greater service flexibility
Mass Storage allows job specific files to be stored in
the control panel such as test and inspection reports,
record drawings, specifications, and more...
Ethernet connectivity options include Building
Network Interface Module (BNIC) and SafeLINC
Internet Interface
RUI (Remote Unit Interface) communications port
supports either Class B or Class A operation for
remote annunciation equipment
Basic Panel Model Selection
Panel
Model
Color
4010-9601
Red
4010-9602(BA)*
Platinum
4010-9603
Red
4010-9604
Platinum
* BA model is assembled in the USA.
Current Notes:
1.
Basic panel current does not subtract from the 6 A output rating.
2.
Supervisory and alarm current specifications are for determining battery standby requirements.
3.
Current specifications include an active RUI channel.
4.
IDNet channel device current is not included, refer to page 7 for details.
5.
IDNAC channel notification appliance current is not included, calculate separately per connected devices.
Language
Listings
Features
& Voltage
Basic 1- Bay Panel with 2x40 LCD
Operator Interface, 6 A ESS/battery
charger, (1) Two-loop Isolated IDNet 2
UL,
English
Communications Channel, Class A or
CSFM,
Class B, with support for up to 250
120 VAC
FM
addressable IDNet points; and two, 3 A,
Class B, IDNAC SLCs with support for
254 addressable notification appliances
UL, ULC,
Same features as above with 48 LED
English
CSFM,
annunciation; alarm current includes 24
120 VAC
FM
annunciator LEDs activated
Basic Panel Description
4010ES panels with ESS include:
An Operator Interface, Master Controller with 2 GB
Compact Flash, IDNet 2 dual loop communications
that provides Class B or Class A operation for up to
250 addressable IDNet points, with dual short circuit
isolating loop outputs, and 6 A Enhanced System
Supply (ESS)
RUI Class B or Class A communications port for
remote annunciation devices
Support for up to 20 internal and external card
addresses
Other standard features may be provided depending
on model (see model selection below for additional
details on specific models)
Cabinet and door
6 A Enhanced System Supply details:
Two, 3 A Class B IDNAC SLCs for up to 254
addressable notification appliances; Class A
operation is available using the 4010-9930 Dual
Class A IDNAC Isolator (DCAI) module
Up to 2 A of auxiliary power
110 Ah (UL)/50 Ah (ULC) battery charger (33 Ah
maximum in the control panel cabinet)
Low Battery Voltage Cutout is selectable when
required (required for ULC listing applications)
2 A for Regulated 24 DC operation; 1 programmable
auxiliary relay rated for 2 A @ 32 VDC
6
Supv.
Alarm
Available
Current
Current
Option
Blocks
(see notes below)
256 mA
390 mA
3
4"x5"
blocks
276 mA
455 mA
S4010-0011-5 11/2015