Assembly - ProMinent MAKRO TZ Operating Instructions Manual

Diaphragm metering pump
Table of Contents

Advertisement

Assembly

6
Assembly
Supporting floor
h
P_MOZ_0016_SW
Fig. 9
Space requirement
A
A
P_MOZ_0018_SW
Fig. 10
1
f
f
f
3
P_MOZ_0017_SW
Fig. 11
18
Position the pump so that control elements such as the stroke length
adjustment knob, the indicating dial A or the oil inspection window are
accessible.
In so doing, ensure there is enough space to carry out an oil change (vent
screws, oil drain plugs, oil trough ...).
1
Discharge valve
2
Dosing head
2
3
Suction valve
Ensure there is sufficient free space (f) around the dosing head as well as
the suction and discharge valve so that maintenance and repair work can
be carried out on these components.
Compare the dimensions on the dimension sheet and
pump.
WARNING!
Danger of electric shock
If water or other electrically conducting liquids penetrate into
the drive housing, in any other manner than via the pump's
suction connection, an electric shock may occur.
Position the pump so that it cannot be flooded.
WARNING!
The pump can break through the supporting floor or slide off
it
The supporting floor must be horizontal, smooth and per‐
manently load-bearing.
Capacity too low
Vibrations can disturb the valves of the liquid end.
The supporting floor must not vibrate.
CAUTION!
Danger from incorrectly operated or inadequately maintained
pumps
Danger can arise from a poorly accessible pump due to
incorrect operation and poor maintenance.
Ensure that the pump is accessible at all times.
Adhere to the maintenance intervals.