READ CAREFULLY AND FOLLOW ALL INSTRUCTIONS FOR YOUR OWN SAFETY
• DISCONNECT AC POWER SUPPLY BEFORE SERVICING.
• Installation and servicing of this equipment should be performed by qualified service personnel only.
• Ensure the electricity connections conform to the National Electrical Code and local regulations if applicable.
• Do not mount near gas or electrical heaters.
• Equipment should be mounted in locations and at heights where it will not readily be subjected to tampering by
unauthorized personnel.
• The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition. Any
modification or use of non-original components will void the warranty and product liability.
• Do not use this equipment for other than intended use.
1. Mount fixture in desired location using the supplied trunnion mounting bracket and appropriate hardware for
application.
2. Unhinge refractor housing by loosing (4) screws and removing reflector.
3. Feed wire leads into fixture through center opening in trunnion.
4. Electrical connection should be made inside fixture. Cap all unused leads to prevent shorting. This
fixture is pre-wired for 277 volt; make sure supply line voltage is 277 volt. For alternate line voltage select proper
ballast lead to match your line voltage.
a. Connect the line fixture lead to the black supply lead.
b. Connect the common fixture lead to the white supply lead.
c. Connect the ground lead from the sevice to green grounding screw.
5. Use approved connectors to connect fixture leads to supply leads and make wire splices inside fixture.
6. Replace reflector, and install lamp.
7. Replace refractor; make sure that the lens gasket is properly seated around the perimeter of the lens to ensure a
weather tight seal.
8. Set desired fixture angle by removing postioning screw, loosing trunnion bolts and rotating trunnion to desired
angle. Then re-insert positioning screw and tighten.
20070062 REV 2 - 10/13
SAVE THESE INSTRUCTIONS!
INSTALLATION INSTRUCTIONS
1
INSTALLATION INSTRUCTIONS
800.533.3948 • www.barronltg.com
TL301

Advertisement

loading

Summary of Contents for BARRON TL301

  • Page 1 TL301 INSTALLATION INSTRUCTIONS SAVE THESE INSTRUCTIONS! READ CAREFULLY AND FOLLOW ALL INSTRUCTIONS FOR YOUR OWN SAFETY • DISCONNECT AC POWER SUPPLY BEFORE SERVICING. • Installation and servicing of this equipment should be performed by qualified service personnel only. • Ensure the electricity connections conform to the National Electrical Code and local regulations if applicable.
  • Page 2 TL301 INSTALLATION INSTRUCTIONS IMPORTANT To weather-proof your outdoor installation, be sure to seal all holes in fixture housing. (Mounting, conduit, plugs, and photo controls, etc) with silicone sealant. TROUBLESHOOTING CHECKLIST 1. Check your power source. 2. If power is on and lamp does not burn. Turn power source off and lock out to prevent power being restored.