Commissioning
7.3 Checks to be carried out prior to commissioning
● All fixing screws, connection elements, and electrical connections have been tightened to
● The operating conditions match the data provided in accordance with the technical
● Moving parts such as the coupling move freely.
● All touch protection measures for moving and live parts have been taken.
● If the second shaft extension is not in use, its feather key is secured to prevent it from being
● The rotor can spin without coming into contact with the stator.
● The bearing insulation is not bridged.
Electrical connection
● The grounding and equipotential bonding connections have been made correctly.
● The machine is connected so that it rotates in the direction specified.
● Appropriately configured control and speed monitoring functions ensure that the motor
● The minimum insulation resistance values are within tolerance.
● Minimum air clearances have been maintained.
● Any supplementary motor monitoring devices and equipment have been correctly
● All brakes and backstops are operating correctly.
● At the monitoring devices, the values for "Warning" and "Shutdown" are set.
● Appropriately configured control and speed monitoring functions ensure that the the
● Any supplementary motor monitoring devices and equipment have been correctly
Converter operation
● If the design of the motor requires connection to a particular converter type, the rating plate
● The converter is correctly parameterized. The parameterization data is specified on the
● Any supplementary motor monitoring devices and equipment have been correctly
86
the specified tightening torques.
documentation, such as degree of protection, ambient temperature, etc..
thrown out, and cut back to roughly half its length if the rotor has balancing type "H"
(standard type). The unused shaft extension is covered and protected against accidental
contact.
cannot exceed the permissible speeds specified in the technical data. For this purpose,
compare the data on the rating plate or, if necessary, the system-specific documentation.
connected and are functioning correctly.
permissible speeds specified on the rating plate cannot be exceeded.
connected and are fully functional.
will contain corresponding additional information.
rating plate of the machine. Information about the parameters is available in the operating
instructions for the converter.
connected and are functioning correctly.
SIMOTICS M-1PH8 1PH818., 1PH822.
Operating Instructions 07/2016