Table A.12 General Specifications
Specification
Dimensions
Storage Temperature
Operating Temperature
Operating Humidity
Operating Altitude
Vibration
Shock
Agency Certification
Hazardous Environment Class
Radiated and Conducted Emissions EN50081-2 Class A
Electrical /EMC:
ESD Immunity (IEC1000-4-2)
Radiated Immunity (IEC1000-4-3)
Fast Transient Burst (IEC1000-4-4)
Surge Immunity (IEC1000-4-5)
Conducted Immunity (IEC1000-4-6)
(1) Conducted Immunity frequency range may be 150 kHz to 30 MHz if the Radiated Immunity frequency range is 30 MHz
to 1000 MHz.
Value
90 mm (height) x 87 mm (depth) x 40.4 mm (width)
height including mounting tabs is 110 mm
3.54 in. (height) x 3.43 in. (depth) x 1.59 in. (width)
height including mounting tabs is 4.33 in.
-40°C to +85°C (-40°F to +185°F)
0°C to +55°C (+32°F to +131°F)
5% to 95% non-condensing
2000 meters (6561 feet)
Operating: 10 to 500 Hz, 5G, 0.030 in. max. peak-to-peak,
2 hours per axis
Relay Operation: 1.5G
Operating: 30G panel mounted, 3 pulses per axis
Relay Operation: 7G
Non-Operating: 50G panel mounted, 3 pulses per axis
(40G DIN Rail mounted)
C-UL certified (under CSA C22.2 No. 142)
UL 508 listed
CE compliant for all applicable directives
Class I, Division 2, Hazardous Location, Groups A, B, C, D
(UL 1604, C-UL under CSA C22.2 No. 213)
The module has passed testing at the following levels:
4 kV contact, 8 kV air, 4 kV indirect
10 V/m, 80 to 1000 MHz, 80% amplitude modulation, +900
MHz keyed carrier
2 kV, 5 kHz
2 kV common mode, 1 kV differential mode
(1)
10V, 0.15 to 80 MHz
Specifications
A-7
Publication 1762-UM001B-EN-P