How To Access The Fault Log; How To Clear The Fault Log - Baldor 18H Series Installation & Operating Manual

Vector drive, ac flux vector control
Table of Contents

Advertisement

Section 1
General Information

How to Access the Fault Log

Action
Apply Power
Press DISP key 5 times
Press ENTER key
Press Y key
Press ENTER key

How to Clear the Fault Log

Action
Apply Power
Press DISP key
Press ENTER key
Press SHIFT key
Press RESET key
Press SHIFT key
Press ENTER key
Press Y or
key
Press ENTER key
MN718
When a fault condition occurs, motor operation stops and a fault code is displayed on
the Keypad display. The control keeps a log of up to the last 31 faults. If more than 31
faults have occurred the oldest fault will be deleted from the fault log to make room for the
newest fault. To access the fault log use the following procedure:
Description
Display mode showing output
frequency
Use DISP key to scroll to the
Fault Log entry point.
Display first fault type and time
fault occurred.
Scroll through fault messages.
Return to display mode.
Use the following procedure to clear the fault log.
Description
Display mode showing output
frequency.
Press DISP to scroll to the Fault
Log entry point.
Displays most recent message.
Fault log is cleared.
Scroll Fault Log Exit.
Return to display mode.
Display
Logo display for 5 seconds.
Display mode.
Typical display.
If no messages, the fault log exit
choice is displayed.
Display mode stop key LED is on.
Display
Logo display for 5 seconds.
Display mode.
No faults in fault log.
Comments
Comments
Troubleshooting 5-3

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents