Section 1
General Information
Table 3-5 Wire Size and Protection Devices - 460 VAC Controls
Control O tp t
Control Output
P
Power Rating
R ti
1
2
3
5
7.5
10
15
20
25
30
40
50
60
75
100
125
150
200
250
300
350
400
450
500
Note: All wire sizes based on 75 C copper wire, 3% line impedance. Higher temperature smaller gauge wire may be
used per NEC and local codes. Recommended fuses/breakers are based on 25 C ambient, maximum
continuous control output current and no harmonic current.
MN718
p
Input
Inp t
p
Breaker
B
k
Fast Acting
4A
10A
10A
10A
15A
20A
25A
30A
40A
45A
60A
70A
90A
125A
150A
175A
200A
250A
350A
400A
500A
600A
600A
800A
1000A
Input Fuse
Inp t F se
Time Delay
4A
3A
5A
4A
8A
6A
12A
9A
20A
15A
25A
17.5A
30A
25A
40A
30A
50A
40A
60A
45A
80A
60A
100A
75A
125A
90A
150A
125A
200A
150A
250A
175A
300A
200A
350A
250A
450A
350A
500A
400A
600A
500A
800A
600A
800A
600A
800A
Wire Ga ge
Wire Gauge
2
AWG
mm
14
2.5
14
2.5
14
2.5
14
2.5
14
2.5
12
4
10
6
8
10
8
10
6
16
4
25
4
25
2
35
1/0
54
2/0
70
2/0
70
4/0
120
(2)1/0
(2)54
(2)3/0
(2)95
(2)4/0
(2)120
(3)4/0
(3)120
(3)250 mcm
(3)125
(3)250 mcm
(3)125
(3)350 mcm
(3)185
Receiving & Installation 3-11