Baldor 18H Series Installation & Operating Manual page 28

Vector drive, ac flux vector control
Table of Contents

Advertisement

Section 1
General Information
Table 3-7 Single Phase Rating Wire Size and Protection Devices - 230 VAC Controls
Control Output
Power Rating
P
R ti
1
2
3
5
7.5
10
15
20
25
30
40
50
Table 3-8 Single Phase Rating Wire Size and Protection Devices - 460 VAC Controls
Control Output
P
Power Rating
R ti
1
2
3
5
7.5
10
15
20
25
30
40
50
60
Note: All wire sizes based on 75 C copper wire, 3% line impedance. Higher temperature smaller gauge wire may be
used per NEC and local codes. Recommended fuses/breakers are based on 25 C ambient, maximum
continuous control output current and no harmonic current.
MN718
p
Input Breaker
p
15A
15A
15A
30A
25A
40A
50A
60A
70A
80A
100A
125A
p
Input Breaker
p
15A
15A
15A
15A
15A
20A
25A
30A
35A
40A
60A
70A
80A
Input Fuse
Fast Acting
Time Delay
5A
5A
10A
10A
15A
15A
30A
30A
25A
25A
30A
30A
45A
45A
45A
45A
70A
70A
80A
80A
100A
100A
125A
125A
Input Fuse
Fast Acting
Time Delay
4A
4A
8A
8A
10A
10A
15A
15A
15A
15A
15A
15A
25A
25A
30A
30A
30A
30A
40A
40A
50A
50A
60A
60A
80A
80A
Wire Gauge
2
AWG
mm
14
2.5
14
2.5
14
2.5
12
4
14
2.5
12
4
10
6
8
10
8
10
6
16
4
25
4
25
Wire Gauge
2
AWG
mm
14
2.5
14
2.5
14
2.5
14
2.5
14
2.5
14
2.5
14
2.5
14
2.5
14
2.5
10
6
8
10
8
10
6
16
Receiving & Installation 3-17