Baldor 18H Series Installation & Operating Manual page 47

Vector drive, ac flux vector control
Table of Contents

Advertisement

Section 1
General Information
Note 1
Note 4
Programmable 0–5V Output (Factory Preset: Speed)
Note 2
Programmable 0–5V Output (Factory Preset: Current)
Notes:
1.
Refer to Analog Inputs.
2.
Refer to Analog Outputs.
3.
Refer to Opto Isolated Outputs.
4.
Refer to Figure NO TAG for 4-20mA.
5.
Refer to Encoder installation.
6.
Refer to Buffered Encoder Output.
Refer to Figure NO TAG.
3-36 Receiving & Installation
Figure 3-21 Standard Run 3-Wire Connection Diagram
5k
Command Pot
5VDC, 10VDC or 4-20mA
Note 3
J1-8
OPEN disables the control and motor coasts to a stop.
CLOSED allows current to flow in the motor and produce torque.
J1-9
MOMENTARY CLOSED starts motor operation in the Forward direction. In JOG mode
(J1-12 CLOSED), continuous CLOSED jogs motor in the Forward direction.
J1-10
MOMENTARY CLOSED starts motor operation in the Reverse direction. In JOG mode
(J1-12 CLOSED), CONTINUOUS closed JOGS motor in the Reverse direction.
J1-11
MOMENTARY OPEN causes motor to decel to stop (depending on Keypad Stop Mode
parameter setting). Motor current continues to be applied to the motor.
J1-12
CLOSED places control in JOG mode, Forward and Reverse run are used to jog the
motor.
J1-13
OPEN selects ACC / DEC / S-CURVE group 1.
CLOSED selects group 2.
J1-14
CLOSED selects preset speed #1, (J1-12, will override this preset speed).
OPEN allows speed command from Analog input #1 or #2 or Jog.
J1-15
CLOSED to reset fault condition.
OPEN to run.
J1-16
OPEN causes an external trip to be received by control. The control will disable and
display external trip when programmed "ON". When this occurs, the motor stop
command is issued, drive operation is terminated and an external trip fault is displayed
on the keypad display (also logged into the fault log).
If J1-16 is connected, you must set Level 2 Protection block, External Trip to "ON".
J1–39 & 40 Jumper as shown to power the Opto Inputs from the internal +24VDC supply.
ANALOG GND
ANALOG INPUT 1
POT REFERENCE
ANALOG INPUT +2
ANALOG INPUT –2
ANALOG OUT 1
ANALOG OUT 2
ENABLE
FORWARD RUN
REVERSE RUN
STOP
JOG
ACCEL/DECEL
PRESET SPEED #1
FAULT RESET
EXTERNAL TRIP
OPTO INPUT COMMON
OPTO OUT COMMON
OPTO OUT #1
OPTO OUT #2
OPTO OUT #3
OPTO OUT #4
Terminal Tightening Torque = 7 Lb-in (0.8 Nm).
J1
1
23
A
2
24
A
3
25
B
4
26
B
5
27
INDEX
6
28
INDEX
7
29
+5VDC
8
30
COMMON
9
A
31
10
A
32
11
B
33
12
B
34
13
INDEX
35
14
INDEX
36
15
Not Used
37
16
38
COMMON
17
39
+24VDC
18
40
OPTO IN POWER
19
41
OPTO OUT #1 RETURN
20
42
OPTO OUT #2 RETURN
21
43
OPTO OUT #3 RETURN
22
44
OPTO OUT #4 RETURN
Encoder
Input
Note 5
Buffered
Encoder
Output
Note 6
MN718