Baldor 18H Series Installation & Operating Manual page 36

Vector drive, ac flux vector control
Table of Contents

Advertisement

Section 1
General Information
Figure 3-10 Size F Single Phase 230/460VAC Power and Motor Connections
Note 1
* Circuit
Breaker
Note 2
B1
*Optional
Note 4
Line
Reactor
B2
Note 2
L1
Series 18H
Control
T1
Note 3
A1
B1
*Optional
Note 5
Load
Reactor
A2
B2
Note 3
Note 3
*Optional
Note 5
Load
Reactor
Note 3
Note 6
M=Contacts of optional M-Contactor
MN718
L1
L2
Earth
C1
* Optional components not provided with 18H Control.
C2
L2
L3
Notes:
Baldor
1.
2.
3.
T2
T3
4.
C1
5.
6.
C2
T2 T3
T1
G
* AC Motor
Optional Connection of
Load Reactor and M-Contactor
T1
T2
T3
A1
B1
C1
A2
B2
C2
M
M
M
T2 T3
T1
G
* Motor
See Recommended Tightening Torques in Section 7.
L1
L2
* Fuse
Connection
B1
C1
See "Protective Devices" described previously in this section.
Shield wires inside a metal conduit.
Metal conduit should be used to shield output wires (between
control and motor).
See "Line Impedance" described previously in this section.
See Line/Load Reactors described previously in this section.
A motor circuit contactor is recommended to provide a positive
disconnect and prevent motor rotation which could pose a safety
hazard. Connect the M-Contactor as shown. The contactor
should open the enable input at J1-8 at least 20 msec before the
main M-contacts open to prevent arcing at contacts. This greatly
increases contactor life and allows use of IEC rated contactors.
Note 60
To Power Source
(Rated Coil
Voltage)
J1
*
Note 6
M Enable
7
8
9
Note 1
* Optional
* M-Contactor
RC Device
Electrocube
RG1781-3
Note: Close "Enable"
after "M" contact closure.
Receiving & Installation 3-25