Section 1
General Information
Block Title
Parameter
MISCELLANEOUS
Homing Speed
continued
Homing Offset
SECURITY
Security State
CONTROL
Access Timeout
Access Code
MOTOR DATA
Motor Voltage
Motor Rated Amps
Motor Rated SPD
Motor Rated Freq
Motor Mag Amps
Encoder Counts
Resolver Speed
CALC Presets
4-18 Programming & Operation
Table 4-3 Level 2 Parameter Block Definitions
Description
In Bipolar and Serial modes, this parameter sets the speed that the motor shaft will
rotate to a "Home" position when the orient input switch is closed (J1-11).
In Bipolar and Serial modes, this parameter sets the number of digital encoder counts
past home at which the motor stop command is issued. Quadrature encoder pulses
are 4 times the number of encoder lines per revolution. The recommended minimum
number is 100 encoder counts to allow for deceleration distance to allow the motor to
stop smoothly.
Note: Homing direction is always forward.
Off - No security Access Code required to change parameter values.
Local - Requires security Access Code to be entered before changes can be made
using the Keypad.
Serial - Requires security Access Code to be entered before changes can be made
using the Serial Link.
Total - Requires security Access Code to be entered before changes can be made
using the Keypad or serial link.
Note: If security is set to Local, Serial or Total you can press PROG and scroll
The time in seconds the security access remains enabled after leaving the programming
mode. If you exit and go back into the program Mode within this time limit, the
security Access Code does not have to be re-entered. This timer starts when leaving
the Program Mode (by pressing DISP).
A 4 digit number code. Only persons that know the code can change secured Level 1
and Level 2 parameter values.
Note: Please record your access code and store it in a safe place. If you cannot
The rated voltage of the motor (listed on the motor nameplate).
The rated current of the motor (listed on the motor nameplate). If the motor current
exceeds this value for a period of time, an Overload fault will occur.
The rated speed of the motor (listed on the motor nameplate). If Motor Rated SPD =
1750 RPM and Motor Rated Freq = 60 Hz, the Keypad Display will show 1750 RPM
at 60 Hz and 875 RPM at 30Hz.
The rated frequency of the motor (listed on the motor nameplate).
The motor magnetizing current value (listed on the motor nameplate). Also called no
load current. Measure using a clamp on amp meter at the AC power line while the
motor is running at line frequency with no load connected to the motor shaft.
The number of encoder feedback counts (lines per revolution).
The speed of the resolver, if a resolver is used for feedback.
This procedure loads preset values into memory that are required to perform Auto Tune.
Always run CALC Presets as the first step of Auto Tune.
through the parameter values that are programmed but you are not allowed
to change them unless you enter the correct access code.
gain entry into parameter values to change a protected parameter, please
contact Baldor. Be prepared to give the 5 digit code shown on the lower
right side of the Keypad Display at the Security Control Access Code
parameter prompt.
Continued
MN718