Section 1
General Information
Table 3-6 Wire Size and Protection Devices - 575 VAC Controls
Control O tp t
Control Output
P
Power Rating
R ti
1
2
3
5
7.5
10
15
20
25
30
40
50
60
75
100
125
150
Note: All wire sizes based on 75 C copper wire, 3% line impedance. Higher temperature smaller gauge wire may be
used per NEC and local codes. Recommended fuses/breakers are based on 25 C ambient, maximum
continuous control output current and no harmonic current.
3-12 Receiving & Installation
p
Input
Inp t
p
Breaker
B
k
Fast Acting
5A
10A
10A
10A
10A
15A
20A
25A
30A
35A
45A
60A
70A
120A
120A
150A
175A
Inp t F se
Input Fuse
Time Delay
5A
4A
5A
4A
6A
5A
10A
7A
15A
10A
15A
12A
25A
20A
35A
25A
40A
30A
50A
35A
60A
45A
80A
60A
90A
70A
150A
120A
150A
120A
200A
150A
225A
175A
Wire Ga ge
Wire Gauge
2
AWG
mm
14
2.5
14
2.5
14
2.5
14
2.5
14
2.5
14
2.5
12
4
10
6
8
10
8
10
6
16
4
25
4
25
3
27
1/0
54
2/0
70
2/0
70
MN718