Size F Single Phase Power Installation - Baldor 18H Series Installation & Operating Manual

Vector drive, ac flux vector control
Table of Contents

Advertisement

Size F Single Phase Power Installation

Place JP2 on the High Voltage Circuit Board across pins 1 and 2.
High Voltage Circuit Board
(150 - 250HP F Size)
JP1
3-24 Receiving & Installation
Figure 3-9 Jumper Configuration
J3
Power and Control Connections
The single phase power and motor connections are shown in Figure 3-10.
1.
Connect the incoming power wires to Main Circuit Terminals L2 and L3.
2.
Place a jumper across control power input terminals L1 and L3. Use the same
size wire for the jumper as the incoming power wires on L2 and L3.
3.
Connect earth ground to the " " of the control. Be sure to comply with local
codes.
Note: Use same gauge wire for earth ground as is used for L1, L2 and L3
connections. Refer to the Wire Size and Protection Devices tables
shown previously in this section.
4.
Connect the three phase power leads of the AC motor to terminals T1, T2, and
T3 of the Main Circuit Terminals.
5.
Connect motor ground wire to the " " of the control. Be sure to comply with all
applicable codes.
Note: In steps 3 and 5 grounding by using conduit or panel connection is not
adequate. A separate conductor of the proper size must be used as a ground
conductor.
J5
1
JP2
Pins 1 & 2 = Single Phase
Pins 2 & 3 = Three Phase
J1
J4
MN718