Download Print this page

Eaton Bussmann Series Installation Manual page 9

Selector and pistol handles for use with 8 mm shafts
Hide thumbs Also See for Bussmann Series:

Advertisement

CCP2-H4X-_ selector and pistol handles for 8 mm shafts
7
Step 7: Fully insert the shaft back into the switch making sure its
indexing corner (largest flat on the shaft) is in the upper left corner
of the switch shaft hole. Torque setscrew to 2.5 N•m (22 lb-in) using
3 mm Allen wrench. Place shaft coupler on the shaft as shown and
torque setscrew to 2.5 N•m (22 lb-in) using 3 mm Allen wrench.
Note the shaft is indexed so the shaft coupler can only be inserted
one way.
8
Step 8: Check the distance the shaft coupler extends beyond the
enclosure's side as shown. If extension is too great, recut shaft
accordingly and reinstall. If too short, install another shaft per
previous instructions.
9
Step 9: Prepare the handle backer plate for mounting by removing
the depth gauge as shown.
3 mm
2.5 N•m
(22 lb-in)
23 mm (0.91")
10
Step 10: Place switch handle on the enclosure's side so that the
protruding screw guides are seated in the four mounting holes. From
the inside, place the backer plate in position and secure with four
supplied Phillips head screws. Torque to 1 N•m (8.9 lb-in) as shown.
11
OFF
ON
OFF
Step 11: Check switch for proper operation in all modes. If not
operating correctly, revisit these installation steps for remedial
action.
NOTE: Side installation (handle mounted on the enclosure's side and
not the door) does NOT provide for an interlock means to prevent
opening the door while the switch is in either the ON or OFF
position. If preventing access to the enclosure's interior is desired
or required by the application, use a locking door latch or install a
suitable hasp to accept a lock.
Installation manual 3A3695
Effective April 2018
Z 2/#2
1 N•m (8.9 lb-in)
Eaton.com/bussmannseries
9