Page 1
BUSSMANN SERIES Effective July, 2015 Instruction Sheet IS10207 Rev 3 Supersedes July 2014 Bussmann series BSPD Type 1 and Type 2 surge protective devices for switchgear and power distribution panels Table of Contents 1.0 Introduction 2.0 Installation 3.0 Operating features 4.0 Troubleshooting...
(e.g., Wye or Delta), configuration and NEMA enclosure rating, as shown in Table 1. To see the complete catalog numbering / product Figure 1. product labels build-a-code system, see Section 6.0, Catalog Number System . Eaton.com/bussmannseries...
Page 3
1.8 Equipment Testing During these fault conditions any electrical Every Bussmann series BSPD unit is tested at the factory for equipment, including an SPD, may be dielectric breakdown. No further SPD testing is required for subjected to voltages, which exceed their installation.
Page 4
1.8 Pruebas al equipo para que la tenga en cuenta antes de instalar Cada unidad de la Bussmann series BSPD es probada en la fábrica cualquier equipo eléctrico en un sistema de por una ruptura dieléctrica. No se necesitan más pruebas para la energía no aterrizados.
Page 5
NE PAS installer le DPS si celui- etc., conformément aux pratiques de sécurité établies. ci a subit une chute ou a été endommagé lors du montage. Eaton.com/bussmannseries...
Figures 2, 3 and 4. Drill the appropriate holes per the product dimensions and use #10 fasteners for Figure 2. 120-200kA Units in a NEMA 1 Enclosure, NEMA 1 enclosures and 1/4” fasteners for NEMA 4X enclosures. Weight = 6.8 lbs (3.1 kg) Eaton.com/bussmannseries...
Page 7
2.60 (66.0) 5.39 (137.0) 250-400kA 4.10 (104.1) 7.68 (195.0) Figure 6. 3-phase, delta units Figure 4. 120-400kA units in a NEMA 4X enclosure, weight = 120-200kA; 14.6 lbs (6.6 kg), 250-400kA; 21.0 lbs (9.5 kg) Figure 7. 3-phase, Wye units Eaton.com/bussmannseries...
Page 8
Note: Red LEDs do NOT indicate power ON/OFF status, just the surge protection status of that phase. On Wye units with a Neutral wire, an additional illuminated Red LED indicates loss of Neutral-to-Ground protection. Eaton.com/bussmannseries...
Application Engineering Team between 7:00 system voltage and type (Wye/Delta) and is properly installed (See a.m. and 5:00 p.m. Central Time, at 1-855-287-7626 or sending an Section 2, Installation ). e-mail to fusetech@eaton.com. Table 2. Troubleshooting Chart Condition Probable Cause...
5th Edition File E316410 Guide VCZA2, CSA Component Acceptance Std. C22.2 No. 8-M1986 File 243397 Seismic withstand capability Meets or exceeds the requirements specific to I.B.C. 2006, C.B.C 2007 and U.B.C Zone 4 Warranty 10 Years (see warranty statement 3A1502 for details at www.cooperbussmann.com/Surge) Eaton.com/bussmannseries...
EMI/RFI filtering providing up to 50dB of noise attenuation from 10kHz to 100MHz Surge counter with reset button 7.0 Warranty The BSPD surge protective devices are warranted to each individual buyer for a period of 10 years. For details, see limited warranty statement 3A1502 online at www.eaton.com/cooperbussmannseries. Eaton.com/bussmannseries...
Need help?
Do you have a question about the Bussmann Series and is the answer not in the manual?