Installation manual 3A3695
Effective April 2018
Front clockwise handle
operation and installation
The following applies to all clockwise
operating selector and pistol switch
handles. Illustrations are of the selector
handle, but apply equally to pistol handle
versions.
Procedures for clockwise handle
catalog numbers:
CCP2-H4X-B1 (selector)
•
CCP2-H4X-R1 (selector)
•
CCP2-H4X-B2 (pistol)
•
CCP2-H4X-R2 (pistol)
•
For installation with switch catalog
numbers:
CCP2R-(pole)-30CC
•
CCP2R-(pole)-30M
•
CCP2R-(pole)-30CF
•
CCP2R-(pole)-60CF
•
CCP2R-(pole)-100CF
•
CCD2R-(pole)-30
•
CCD2R-(pole)-60
•
CCD2R-(pole)-100
•
CCP2RL-(pole)-30CC
•
CCP2RL-(pole)-30M
•
CCP2RL-(pole)-30CF
•
CCP2RL-(pole)-60CF
•
CCP2RL-(pole)-100CF
•
CCD2RL-(pole)-30
•
CCD2RL-(pole)-60
•
CCD2RL-(pole)-100
•
And either shaft catalog numbers:
CCP2-SH1-290
•
CCP2-SH1-490
•
4
Eaton.com/bussmannseries
CCP2-H4X-_ selector and pistol handles for 8 mm shafts
Switch operating modes
OFF
Handle interlock defeat operation
To be performed only by qualified personnel.
OFF
Handle lock ON operation
Note: NOT to be utilized when switch is applied as a means for emergency stop.
ON
OFF
OFF
2 mm Allen wrench (selector handles) 2.5 mm Allen wrench (pistol handles) 3 N•m (27 lb-in)
To enable the handle's lock ON feature:
Use a 2 mm (selector handle) or 2.5 mm (pistol handle) Allen wrench to loosen the setscrew
•
and remove the handle from the handle base as shown.
Using needle nose pliers, break off the retaining stop on the switch handle bezel as shown.
•
Place handle back onto the handle base and tighten the setscrew.
•
OFF
ON
OFF
ON
ON
ON
ON
Break out this
portion of
ON
the bezel
OFF