7.4.1 Supply air volumetric flow setting
1. Connect the voltmeter (measurement
range U
1...10 V) to connector pins
DC
1 and 3 (GND).
2. Select the corresponding ventilation level
1, 2 or 3 on the room air control (operator
unit).
3. Deactivate the CO2 sensor
(jumper 10 = open).
4. You can now set the defined voltage for
the required supply air volumetric flow for
the selected ventilation level (1, 2 or 3)
with one of the blue potentiometer
adjusters S1, S2 or S3.
You will find the defined voltage value for
the required volumetric flow in the table in
Chapter 7.3 (predefined voltage = f (volu-
metric flow).
Blue adjuster S1 for the predefined
voltage of ventilation level 1
Blue adjuster S2 for the predefined
voltage of ventilation level 2
Blue adjuster S3 for the predefined
voltage of ventilation level 3
7.4.2 Exhaust air volumetric flow setting
1. Connect the voltmeter (measurement
range U
1...10 V) to connector pins 5
DC
and 3 (GND).
2. Proceed exactly as described for supply air
volumetric flow setting and adjust the
defined voltage for the required exhaust air
volumetric flow with one of the red poten-
tiometer adjusters S1, S2 or S3.
Red adjuster S1 for the predefined voltage
of ventilation level 1
Red adjuster S2 for the predefined voltage
of ventilation level 2
Red adjuster S3 for the predefined voltage
of ventilation level 3

8. Accessories

Accessory / Product type
10x WSG 170 air filter,
class G4
Push-in frame WSG-ES 170
for G4 air filter
1x WSF 170 pollen filter,
class F7
1x WSF-AKF 170 active
carbon air filter, class F7
Temperature sensor with
grommet NTC 15
RLS 1 WR room air control
RLS D1 WR digital control
SKD CO
sensor
2
VOC sensor: EAQ 10/2 air
quality controller
Heat exchanger:
Right-hand version
Left-hand version
Enthalpy heat exchanger
(there is only one version
for left and right)
Combi wall support, right-
hand version, suitable for
WS 170 R, WS 170 KR
and WS 170 KBR
KWH 12 R
KWH 16 R
Combi wall support, left-
hand version, suitable for
WS 170 L, WS 170 KL and
WS 170 KBL:
KWH 12 L
KWH 16 L
Plug connector with lip seal
SVR 125
B90-125
pipe elbow
7. Start-up │ UK
Article no.
0093.0270
0093.0269
0093.0271
0093.0272
0157.0833
0157.0809
0157.0828
0157.0345
0157.0834
E192.0570.9000
E192.0570.9100
E192.0612.9000
0152.0058
0152.0060
0152.0059
0152.0061
0055.0183
0055.0312
65

Advertisement

Table of Contents
loading

Table of Contents