Appendix A Specifications; Ethernet Connection; Serial Interfaces; Power Supply - HMS Anybus Modbus-TCP/RTU Gateway User Manual

Hide thumbs Also See for Anybus Modbus-TCP/RTU Gateway:
Table of Contents

Advertisement

Specifications

Ethernet Connection

10BASE-T or 100BASE-TX (IEEE 802.3). RJ45 connector.

Serial Interfaces

EIA-232 with full modem control (RTS, CTS, DCD, DTR, DSR, RI), 300-115200 bps, 9-pole DSUB
connector
EIA-485, 300-115200 bps, connection through screw terminal block

Power Supply

9 - 28 VAC/DC
70 mA@24 VDC (1.7 W).

Environmental Specification

Operating temp:
Storage temperature:
Humidity range:

Cover Material

Grey plastic, LEXAN 940, self-extinguishing acc. to UL94-V0

Mounting Option

DIN rail (EN 50022)
Anybus® Modbus TCP/RTU Gateway
Doc.Rev. 2.03
- 40 - 65 °C
- 40 - 85 °C
5 - 93%, non-condensing