Table 51 - Voltage Monitoring Values for Feedback Device
Feedback Devices
20-750-UFB
Not monitored
7V...12V
Primary
4.75V...5.25V
Not monitored
7V...12V
Secondary
4.75V...5.25V
Motion Safety>Secondary Feedback Category
If the Safety Instance is configured for Dual Feedback monitoring, the
Secondary Feedback must be configured. The attributes for the Secondary
Feedback configuration are the same as the Primary Feedback. See the
Safety>Primary Feedback Category
that can be configured for the Secondary Feedback Instance.
IMPORTANT The secondary feedback is intended to provide diagnostic coverage of the
primary encoder. The data produced by the secondary feedback device is not
safety data.
Rockwell Automation Publication 750-UM005A-EN-P - October 2018
Integrated Motion – Configuration, Programming, and Operation
20-750-DENC
Not monitored
4.75V...5.25V
7V...12V
11.4V...12.6V
Not monitored
4.75V...5.25V
7V...12V
11.4V...12.6V