4.2 EtherNet/IP Transmission Definition
4.2.2 Connection List Tab Page
Setting (Detail) button
13
When Scanner is selected, clicking this button will open the IO Communication Detail Setting window where
I/O communication details are set for the selected device.
When Adaptor is selected, the IO Communication Detail Setting window is not displayed even if this button is
clicked.
 For details of the IO Communication Detail Setting window, refer to 4.2.3 IO Communication Detail Setting
Window on page 4-10.
EM Communication Setting
Enable
14
Set enable or disable for explicit message communication. Entering a check mark in this field will enable explicit
message communication. Setting is not possible when Adaptor is selected.
Comment
15
A comment within 16 characters can be entered as desired.
( 2 ) Cautions on Setting Instance No. [IN] and Instance No. [OUT]
Restrictions on Duplication
The following restrictions are applied to the instance numbers.
• The input instance number and output instance number must not be duplicated at the same connection number.
• For Scanner, duplication of input and output instance numbers is permitted if the connection number differs.
• For Adaptor, duplication of input and output instance numbers is not permitted even if the connection number
differs.
An error will occur when saving the settings if the restrictions above are not observed.
Instance Number and Size for Scanner
When setting the instance number and size for Scanner, the input/output instance numbers and sizes must agree with
those set for Adaptor at the remote station. The setting is replaced as shown in examples below. That is, the input set-
ting of Adaptor at the remote station is replaced with the Scanner output setting, and the output setting of Adaptor at the
remote station is replaced with the Scanner input setting.
<Examples>
If the Adaptor setting at remote station is: Input instance number 100 and Size 100, Output instance number
then, the Scanner setting must be: Input instance number 101 and Size 50, Output instance number 100 and
( 3 ) Deleting the Assigned Devices
The following explains the procedure for deleting the devices assigned to the list.
 Care should be taken in assignment deletion. The deleted assignment cannot be restored.
1.
Click any cell of the device to be deleted on the Connection List tab page.
4-8
101 and Size 50,
Size 100.