Necessary or useful accessories Information on environmentally sound usage Text designations: • Activities which may be carried out in any sequence. 1. Activities which should be carried out in the specified sequence. – General lists Festo – GDCP-CMGA-E1-EN – 1404a...
The warranty and safety certifications are null and void if the modules have been manipulated. The CMGA can be operated in a temperature range between 0° and 50 °C. Make sure that this temper- ature range is not exceeded. Festo – GDCP-CMGA-E1-EN – 1404a...
Commissioning or modification of an installation of the CMGA can only be performed by qualified per- sonnel! Contact the company that produced the safety-relevant test report. Changing the configuration can cause the module to lose its safety function. Festo – GDCP-CMGA-E1-EN – 1404a...
CMGA-E1 Commissioning The CMGA-E1 is an input/output extension module that can only be used in combination with a CMGA basic module (i.e. CMGA-B1-M0-L0-A0, CMGA-B1-M1-L1-A0 or CMGA-B1-M2-L2-A0). It is connected to the basic module via the backwall bus. CMGA-B1-M2-L2-A0 CMGA-E1 CMGA-E1-CO Fig.
Page 7
Digital input 07 (I1.7) X23:4 IN08 Digital input 08 (I1.8) X24:1 IN09 Digital input 09 (I1.9) X24:2 IN10 Digital input 10 (I1.10) X24:3 IN11 Digital input 11 (I1.11) X24:4 IN12 Digital input 12 (I1.12) Tab. 1 Connections Festo – GDCP-CMGA-E1-EN – 1404a...
Fig. 5 CMGA-E1 In this window, write the serial number of the CMGA-E1 (see rating plate) into the field “Device 1”. The value of the input field “Device 2” must be different from “Device 1” and must not be zero.
Page 9
CMGA-E1 Fig. 6 Device configuration Configure IO01 as input Configure IO02 as output Fig. 7 Example Festo – GDCP-CMGA-E1-EN – 1404a...
Only the operating status 4 = RUN makes it possible to operate the machine or system. Only then are all configured safety functions active. If the CMGA is in the mode “Alarm” = A or in the mode “Failure” = F, all safety-relevant outputs are deactivated. Festo – GDCP-CMGA-E1-EN – 1404a...
If an alarm or fatal error occurs more frequently, contact the company that installed the machine or system. All error codes of the CMGA basic module, including the one from the CMGA-E1, are shown in the dis- play of the basic unit.
Page 12
CMGA-E1 CMGA-E1 specific error codes that are not listed in the CMGA installation instructions Alarm code A 2101 / A 2101 Description Error in transmission telegram, basic unit Cause Basic unit does not receive an answer from CMGA-E1 Remedy Check installation between basic unit and CMGA-E1...
Page 13
CMGA-E1 CMGA-E1 specific error codes that are not listed in the CMGA installation instructions Fatal error code F 3829 Description Status of the output EAA1.5 is incorrect Remedy Check the output circuit (short circuit) Check the configuration (input or output)
9. Switch on the supply voltage. Note: Plug-in connections of the CMGA module must not be disconnected or reconnected when powered. There is a danger of sensor damage, particularly with connected position or speed sensors. Festo – GDCP-CMGA-E1-EN – 1404a...
1) Value valid only for extension module. For an overall evaluation as per EN ISO 13849, a series connection to the respective basic module must be applied. = PFH + PFH Logic Basic Extension Tab. 6 Festo – GDCP-CMGA-E1-EN – 1404a...
Page 16
Internet: prohibited. Offenders will be liable for damages. All rights www.festo.com reserved in the event that a patent, utility model or design patent is registered. Original: de Version: 1404a Festo – GDCP-CMGA-E1-EN – 1404a...