Product Certifications
July 2016
Special Condition for Safe Use (X):
1. The surface resistivity of the antenna is greater than
1 G. To avoid electrostatic charge build-up, it must
not be rubbed or cleaned with solvents or a dry cloth.
2. The power module may be replaced in a hazardous
area. The power module has a surface resistivity
greater than 1 G and must be properly installed in
the wireless device enclosure. Care must be taken
during transportation to and from the point of
installation to prevent electrostatic charge build-up.
International
I7
IECEx Intrinsic Safety
Certificate: IECEx BAS 07.0007X
Standards: IEC 60079-0: 2011, IEC 60079-11: 2011
Markings: Ex ia IIC T4 Ga, T4 (–60 °C  T
Ex ia IIC T5 Ga, T5 (–60 °C  T
Sensor terminal parameters
U
= 6.6 V
O
I
= 26.2 mA
O
P
= 42.6 mW
O
C
= 11 μF
o
L
= 25 mH
o
Special Conditions for Safe Use (X):
1. The surface resistivity of the antenna is greater than
1 G. To avoid electrostatic charge build-up, it must
not be rubbed or cleaned with solvents or a dry cloth.
2. The Model 701PBKKF Power Module may be replaced
in a hazardous area. The Power Modules have a
surface resistivity greater than 1 G and must be
properly installed I the wireless device enclosure. Care
must be taken during transportation to and from the
point of installation to prevent electrostatic charge
build-up.
3. The Rosemount 648 Wireless enclosure may be made
of aluminum alloy and given a protective
polyurethane paint finish; however, care should be
taken to protect it from impact or abrasion if located
in a Zone 0 area.
Brazil
I2
INMETRO Intrinsic Safety
Certificate: UL-BR 15.0140X
Standards: ABNT NBR IEC 60079-0:2008 + Errata
1:2011, ABNT NBR IEC60079-11:2009
Markings: Ex ia IIC T4 (–60 °C  T
Ex ia IIC T5(–60 °C  T
Product Certifications
Special Condition for Safe Use (X):
China
I3
 +70 °C)
a
 +40 °C)
a
Special Condition for Safe Use (X):
Japan
I4
Special Condition for Safe Use (X):
 +70 °C),
a
+40 °C) IP66
a
Sensor terminal parameters
U
= 6.6 V
O
I
= 26.2 mA
O
P
= 42.6 mW
O
C
= 11 μF
o
L
= 25 mH
o
1. See certificate for special conditions.
China Intrinsic Safety
Certificate: GYJ11.1706X
Standards: GB3836.1-2010,
GB3836.4-2010,
GB3836.20-2010
Markings: Ex ia IIC T4/T5 Ga
T code
Ambient temperature
–60 °C  T
T4
–60 °C  T
T5
Sensor terminal parameters
U
= 6.6 V
O
I
= 26.2 mA
O
P
= 42.6 mW
O
C
= 11 μF
O
L
= 25 μF
O
1. See certificate for special conditions.
TIIS Intrinsic Safety
Certificates: TC18638
Markings: Ex ia IIC T4 (–20
1. See certificate for special conditions.
Sensor terminal parameters
U
= 6.6 V
O
I
= 26.2 mA
O
P
= 42.6 mW
O
C
= 11 μF
O
L
= 25 μF
O
Reference Manual
00809-0200-4648, Rev BB
 +70 °C
a
 +45 °C
a
+60 °C)
~
71