To configure the process alerts with a Field Communicator, perform the following
procedure:
1.
2.
3.
4.
5.
2.10

Remove power module

After the sensor and network have been configured, remove the power module and replace
the transmitter cover. The power module should be inserted only when the device is ready
to be commissioned. Use caution when handling the power module. The power module
may be damaged if dropped from heights in excess of 20 feet.
Configuration
Alert "OFF"
Alert "ON"
Deadband
Time
Alert "OFF"
Alert "ON"
Deadband
Time
From the HOME screen, follow the Fast Key sequence, 2 Configure, 1 Guided
Setup, 7 Configure Process Alarms.
Select 2 for Hi-Hi Alarm, or
Select 3 for Hi Alarm, or
Select 4 for LO Alarm, or
Select 5 for LO-LO Alarm and press Enter.
If the alarm is disabled, select 1 Enable and press Enter. If the alarm was previously
enabled, select 2 Leave Enabled and press Enter.
Enter the alarm limit and press Enter.
Enter the alarm deadband and press Enter.
Alert "OFF"
Alert Set Point
Assigned Value
Assigned Value
Alert "OFF"
Alert Set Point
Configuration
July 2016
25