Basic Installation Procedures
Step 5: Connecting AC Output to an Existing AC Circuit
WARNING
FIRE, SHOCK, AND ENERGY HAZARDS
Make sure wiring is disconnected from all electrical sources before
handling. All wiring must be done in accordance with local and national
electrical wiring codes.
Failure to follow these instructions can result in death or serious injury.
NOTICE
EQUIPMENT DAMAGE
Do not connect any AC source (such as a generator or utility power) to
the AC output wiring of the Freedom X.
The Freedom X will not operate if its output is connected to AC voltage
from another source, and potentially hazardous or damaging conditions
may occur. These conditions can occur even if the inverter is off.
Failure to follow these instructions can damage the unit and/or equipment.
Do not connect the Freedom X to an AC branch circuit that has
high-power consumption loads.
The Freedom X will not operate electric heaters, air conditioners,
stoves, and other electrical appliances that consume more than 1200
watts.
22
A manufacturer-tested and approved GFCI must be connected to the
Freedom X AC output, and GFCI protection must be provided on
every receptacle connected to the AC hard wired installation. Other
types may fail to operate properly when connected to the Freedom
X. See "Ground Fault Circuit Interrupters (GFCIs)" on page 14.