Freedom X Owners Guide.book Page 42 Wednesday, May 11, 2016 10:32 AM
Freedom X Inverter Configuration

To change the Low Battery Cutout (LBCO) voltage:

By default the operational mode is set to 10.5V (" || ").
1.
Press and hold the
button for three seconds.
2.
Press the Scroll
button until the left LCD Screen flashes
" ||" intermittently.
3.
Press the
button to select the setting.
The right LCD Screen will display the current setting "|| "
and then begin to flash intermittently.
 to
This range is from 10.5 to 12.1 volts with

increments of 0.1.
4.
Continue pressing the Scroll
settings until you reach the desired setting.
5.
Press the
button to make the setting permanent.
or
Press the
button to exit.
42

To change the LBCO Shutdown delay timer:

By default the operational mode is set to 300 seconds (" || ").
1.
2.
3.
button to cycle through the
4.
5.
Press and hold the
button for three seconds.
Press the Scroll
button until the left LCD Screen flashes
" ||" intermittently.
Press the
button to select the setting.
The right LCD Screen will display the current setting "|| "
and then begin to flash intermittently.
 to
This range is from 1 to 300 seconds with

increments of 1 (from 1 to 20) then
increments of 10 (from 20 to 300).
Continue pressing the Scroll
settings until you reach the desired setting.
Press the
button to make the setting permanent.
or
Press the
button to exit.
button to cycle through the
Freedom X Owner's Guide