MTU 12V4000G34F Operating Instructions Manual page 106

Table of Contents

Advertisement

1050 – AL Inj. Drift Limit 1 Cyl. B9
Cause
The drift correction for
energization (start and duration)
of injector B9 has violated limit 1.
The injector has soon reached its
maximum drift limit.
1051 – AL Inj. Drift Limit 1 Cyl. B10
Cause
The drift correction for
energization (start and duration)
of injector B10 has violated limit
1. The injector has soon reached
its maximum drift limit.
1052 – AL Inj. Drift Limit 2 Cyl. A1
Cause
The drift correction for
energization (start and duration)
of injector A1 has violated limit 2.
The injector has reached its
maximum drift limit.
1053 – AL Inj. Drift Limit 2 Cyl. A2
Cause
The drift correction for
energization (start and duration)
of injector A2 has violated limit 2.
The injector has reached its
maximum drift limit.
1054 – AL Inj. Drift Limit 2 Cyl. A3
Cause
The drift correction for
energization (start and duration)
of injector A3 has violated limit 2.
The injector has reached its
maximum drift limit.
1055 – AL Inj. Drift Limit 2 Cyl. A4
Cause
The drift correction for
energization (start and duration)
of injector A4 has violated limit 2.
The injector has reached its
maximum drift limit.
106 | Troubleshooting | MS15060/01E 2018-12
Corrective action
u Schedule an injector replacement.
Corrective action
u Schedule an injector replacement.
Corrective action
u Replace injector (→ Page 134).
Corrective action
u Replace injector (→ Page 134).
Corrective action
u Replace injector (→ Page 134).
Corrective action
u Replace injector (→ Page 134).