Festo CPV...-GE-CO3-8 series Electronic Manual page 102

Valve terminal with direct connection
Table of Contents

Advertisement

A. Technical appendix and accessories
Load voltage for solenoid CPV valves
Pin 2
Load voltage connection
– Nominal value
– Tolerance
Current consumption
– Nominal value
– Tolerance
Residual ripple
Operating voltage for bus interface
Sub-D plug: Pin 9
M12 adapter: Pin 2
Screw terminal adapter: Pin 5
– Nominal value
– Tolerance
– Current consumption
CPI system
Version
– No. of CP strings
– Cable length per CP string
– Number of CPI/CP modules per CP string
– Number of inputs/outputs per CP string
– Update time
– all CP strings assigned exclusively with modules
with extended functions
– mixed string assignment
– Supports the extended functions of the CPI system
Maximum current consumption on the CP string
Short circuit protection
A-4
24 V DC (protected against reverse polarity)
20.4 ... 26.4 V
sum of all switched-on CP solenoid valves;
see manual "CPV pneumatics"
4 Vpp (within tolerance)
24 V DC (protected against reverse polarity)
11 ... 30 V
max. 30 mA
1
max. 10 m (see Tab. 1/14 and Tab. 1/15)
max. 4
32 I / 32 O
max. 2 ms
max. 4 ms
yes
max. 1.6 A at 24 V
automatic voltage return
Festo P.BE-CPV-CO3-EN en 1201a

Advertisement

Table of Contents
loading

Table of Contents