General characteristics
Nominal power (VA)
Active Power (W)
Technology
Waveform
Bypass
Transfer time AC to DC
Input characteristics
Input connection
Rated input voltage
Range of input voltage
Rated input frequency
Maximum input current
Total harmonic distortion
of the input current
Input power factor
Number of input phases
Output characteristics
Outlets
Rated output voltage
Rated output frequency
Crest factor
68

7 Technical specifications

3 101 73
5000
5000
on-line, double conversion, VFI-SS-111
sinusoidal
internal automatic bypass
external maintenance bypass (optional)
0 ms
Terminal strips
230 V
from 176 V to 280 V at full load
50 / 60 Hz ± 5 %
27.5 A
THDi < 3%
≥ 0.99 (with full linear load)
Single-phase
(8) 10A,
IEC 320-C13
+
(2) 16A
IEC 320-C19
+
terminal strips
230 V ± 1%
adjustable to 200/208/220/230/240 V
50 / 60 Hz ± 0,1%
3:1
3 101 74
6000
6000
33 A