Instructions To Ensure That The Relay Can Be Commissioned At The Specific Settings For The Application - GE MFAC 14 User Manual

High impedance differential relay
Table of Contents

Advertisement

there is a small further movement of the armature. This ensures that contact follow
through and wiping action is present. On units fitted with hand reset flag indicators,
check the flag is free to fall before, or just as, any normally open contacts touch.
Check that the external wiring is correct to the relevant relay diagram or
scheme diagram. The relay diagram number appears inside the case.
Particular attention should be paid to the correct wiring and value of any external
resistors indicated on the wiring diagram/relay rating information.
Note that shorting switches shown on the relay diagram are fitted internally
across the relevant case terminals and close when the module is withdrawn. It is
essential that such switches are fitted across all CT circuits.
If a test block type MMLG is provided, the connections should be checked to the
scheme diagram, particularly that the supply connections are to the 'live' side of the
test block (coloured orange) and with terminals allocated with odd numbers (1, 3, 5,
7, etc.).
Earthing.
Ensure that the case earthing connection above the rear terminal block, is used
to connect the relay to a local earth bar.
Insulation.
The relay, and its associated wiring, may be insulation tested between:
a) all electrically isolated circuits
b) all circuits and earth
An electronic or brushless insulation tester should be used, having a dc voltage
not exceeding 1000V. Accessible terminals of the same circuit should first be
strapped together.
Deliberate circuit earthing links, removed for the tests, must subsequently be
replaced. Terminal allocation.
Terminals of the relay are normally allocated as below, but reference should
always be made to the relevant diagram.
a) Single pole relays
Normally open contacts 1, 3 and 2, 4.
AC current input – 27, 28.
An alternative version of the relay has additional normally open contacts
connected to 5, 7 and 6, 8.
b) Triple pole relays
Normally open contacts 1, 3 and 2, 4.
The contacts are normally connected in parallel for the three phases but
a version of the relay having contacts brought out separately is available.
AC current inputs - 23, 24 : 25, 26 : 27, 28.
2.2
Instructions to ensure that the relay can be commissioned at the specific
settings for the application
It is only necessary to check the relay at the setting on which it is to be used.
The relay must not be used at any setting other than that for which the setting has
been calculated.
12

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mfac 34

Table of Contents