Voltage and current connections should be made using insulated crimp
terminations to ensure that terminal block insulation requirements are maintained for
safety. To ensure that wires are correctly terminated, the correct crimp terminal and
tool for the wire size should be used.
Before energising the equipment it must be earthed using the protective
earth terminal, or the appropriate termination of the supply plug in the case of plug
connected equipment. Omitting or disconnecting the equipment earth may cause a
safety hazard.
The recommended minimum earth wire size is 2.5mm
the technical data section of the product documentation.
Before energising the equipment, the following should be
checked:
Voltage rating and polarity;
CT circuit rating and integrity of connections;
Protective fuse rating;
Integrity of earth connection (where applicable)
Remove front plate plastic film protection
Remove insulating strip from battery compartment
3.
EQUIPMENT OPERATING CONDITIONS
The equipment should be operated within the specified electrical and environmental
limits.
3.1
Current transformer circuits
Do not open the secondary circuit of a live CT since the high level voltage produced
may be lethal to personnel and could damage insulation.
3.2
External resistors
Where external resistors are fitted to relays, these may present a risk of electric
shock or burns, if touched.
3.3
Battery replacement
Where internal batteries are fitted they should be replaced with the
recommended type and be installed with the correct polarity, to avoid possible
damage to the equipment.
3.4
Insulation and dielectric strength testing
Insulation testing may leave capacitors charged up to a hazardous voltage. At
the end of each part of the test, the voltage should be gradually reduced to zero, to
discharge capacitors, before the test leads are disconnected.
3.5
Insertion of modules and pcb cards
These must not be inserted into or withdrawn from equipment whist it is
energised since this may result in damage.