168
n AHU General input/output
1) Total OnOff (AHU)
Function
Input
Using NV network variable : SNVT_switch, nviTotalOnOff
Operation Total OnOff control
h Valid Range
NV
Field
value
SNVT_switch
state
2) Total Temperature (AHU)
Function
Input
Using NV network variable : SNVT_switch, nviTotalTemp
Operation Total Temperature control
h Valid Range
NV
SNVT_temp_p
3) Temperature Unit (AHU)
Function
Input
Using NV network variable : SNVT_switch, nviTempUnit
Operation Temperature Unit control
Function
Output
Using NV network variable : SNVT_switch, nvoTempUnit
Operation Temperature Unit monitor
h Valid Range
NV
Field
value
SNVT_switch
state
Total OnOff input
not used (set in 0% usually)
Total Temperature input
Temperature Unit input
Temperature Unit output
not used (set in 0% usually)
Operation
0 = Total Off
1 = Total On
Operation
18 ~ 30 °C
Operation
0 = Celcius
1 = Fahrenheit