Network Variables
n Air conditioner, ERV, ERV DX, AWHP input/output
1) On/Off (Air conditioner, ERV, ERV DX, AWHP)
Function
Input
Using NV network variable : SNVT_switch, nviOnOff
Operation On/Off control
Function
Output
Using NV network variable : SNVT_switch, nvoOnOff
Operation On/Off monitor
h Valid Range
NV
Field
value
SNVT_switch
state
2) Operation Mode (Air conditioner, ERV, ERV DX, AWHP)
Function
Input
Using NV network variable : SNVT_hvac_mode, nviHeatCool
Operation Operation Mode control
Function
Output
Using NV network variable : SNVT_hvac_mode, nvoHeatCool
Operation Operation Mode monitor
h Valid Range
NV
Field
value
SNVT_hvac
_mode
state
On/Off input
On/Off display
not used (set in 0% usually)
Operation Mode input
Operation Mode display
not used (set in 0% usually)
HVAC_DEHUMID = Dehumid
Operation
0 = OFF
1 = ON
Operation
HVAC_AUTO = Auto
HVAC_HEAT = Heat
HVAC_COOL = Cool
HVAC_FAN_ONLY
= FAN (Air conditioner, AWHP)
= Normal (ERV, ERV DX)