Setting the functions of the ACP Lonworks

The following functions can be set by using the menu of the ACP Lonworks:
- Select Peak or Demand
- Web screen language selection
- Schedule function
- Power display function
- Error history display function
- Outdoor unit cycle information display function
- Setting the attributes of CH6 (not supported in Standard)
- Setting whether to use air conditioner 0.5°C control function

Before setting the functions of the ACP Lonworks

The function setting of the ACP Lonworks should be changed depending on the case that only
the ACP Lonworks is used or the case that the ACP Lonworks is interconnected with the exter-
nal devices such as AC Manager, power distribution indicator, and Demand controller.
In general, the function of the ACP Lonworks should be set and used as follows:
Peak or demand selection
function
Schedule function
Power display function
CAUTION
!
Setting to use the power display
• If the ACP Lonworks and the power distribution indicator are not connected, the power
display function should be set to no-use.
• If it is set to use, be careful since the control speed of the ACP Lonworks will be slower.

Selecting Peak or Demand

The ACP Lonworks offers the function to manage the power consumed by the connected air
conditioner, by which the electric charges can be effectively saved. The ACP Lonworks offers
two functions to limit the maximum power consumption of the air conditioner as follows:
- Peak: The maximum power consumption of the air conditioner can be managed by setting the
maximum usage operation ratio in the ACP Lonworks.
- Demand: It is set when it interfaces with AC Manger.
When this function is set, the maximum usage operation ratio can be set in AC Manager to
manage the maximum power consumption of the air conditioner.
When only ACP Lonworks is
used
Set to peak function
Set to use schedule function
Set to use if it interfaces with power distribution indicator, and
set to no-use if it does not interface..
Installing ACP Lonworks
When ACP Lonworks interfaces
with AC Manager
Set to demand function
Set to no-use of schedule
function
89

Advertisement

Table of Contents
loading