n Air conditioner, ERV, ERV DX, AWHP General input/output
1) Peak Convert Cycle (Air conditioner)
Function
Input
Using NV network variable : SNVT_count, nviPeakSwTime
Operation Peak Convert Cycle control
Function
Output
Using NV network variable : SNVT_count, nvoPeakSwTime
Operation Peak Convert Cycle monitor
h Valid Range
NV
SNVT_count
2) Peak Setting (Air conditioner)
Function
Input
Using NV network variable : SNVT_lev_percent, nviPeakTgtRate
Operation Peak Setting contorl
Function
Output
Using NV network variable : SNVT_lev_percent, nvoPeakTgtRate
Operation Peak Setting monitor
h Valid Range
NV
SNVT_lev_percent
3) Temperature Unit (Air conditioner, ERV DX)
Function
Input
Using NV network variable : SNVT_switch, nviTempUnit
Operation Temperature Unit control
Function
Output
Using NV network variable : SNVT_switch, nvoTempUnit
Operation Temperature Unit monitor
h Valid Range
NV
Field
value
SNVT_switch
state
Peak Convert Cycle input
Peak Convert Cycle display
Peak Setting input
Peak Setting display
Temperature Unit input
Temperature Unit display
not used (set in 0% usually)
Operation
300~900 sec
Operation
0 ~ 100 %
Operation
0 = Celcius
1 = Fahrenheit