Installing ACP Lonworks
120
ACP Lonworks status monitoring after executing lock all and temperature lock
Run LG ACCS of the ACP Lonworks to select all indoor units, and execute lock all function.
Afterwards, execute temperature lock function again, and monitor the status of the ACP
Lonworks.
Check the status of the ACP Lonworks according to the following flowchart.
After selecting all indoor units,
execute lock all and temperature
released in some
released in some
Insert 2PIN connector into PI485.
Check outdoor unit S/W version
through MV and perform
on-boarding (upgrade) of the
program to Version34 or higher.
Carry out on-boarding of PI485
software or check the number to
replace with product with the
Check if the indoor unit power is
shut down. If indoor unit is reset,
lock all will be released, so execute
lock
Are lock all
indoor units?
Yes
Are lock all
indoor units?
No
function.
lock all again.
Is the
No
temperature lock
unlocked?
When you set the system in ACP
Lonworks or AC Manager, temperature
lock (individual lock) is unlocked, so
execute temperature lock (individual
lock) again.
Yes
Yes