Parameter Descriptions

5 Parameter Descriptions

5.1 Cascade Controller Parameters

NOTICE
If one of the Cascade Controller options is used to
extend the number of pumps in a Basic Cascade, the
parameters in parameter group 25-** have to be used.
See VLT AQUA
information.
5
5
3-02 Minimum Reference
Range:
Size
[ -999999.999 -
related
par. 3-03
*
ReferenceFeed-
backUnit]
3-03 Maximum Reference
Range:
Size
[ par. 3-02 -
related
999999.999
*
ReferenceFeed-
backUnit]
3-15 Reference 1 Source
Option:
22
®
Drive Programming Guide for further
Function:
Enter the minimum reference. The
minimum reference is the lowest
value obtainable by summing all
references.
Minimum reference is active only
when 3-00 Reference Range is set to
[0] Min.- Max.
The minimum reference unit
matches:
The configuration of
1-00 Configuration Mode
Configuration Mode: for [1]
Speed closed loop, RPM; for
[2] Torque, Nm.
The unit selected in
3-01 Reference/Feedback
Unit.
Function:
Enter the Maximum Reference. The
Maximum Reference is the highest
value obtainable by summing all
references.
The Maximum Reference unit
matches:
The choice of configu-
ration in
1-00 Configuration Mode:
for [1] Speed closed loop,
RPM; for [2] Torque, Nm.
The unit selected in
3-00 Reference Range.
Function:
Select the reference input to be used
for the first reference signal.
MI38C402 - VLT
®
VLT
AQUA Drive MCO 101/MCO 102
3-15 Reference 1 Source
Option:
[0]
No function
[1]
Analog input 53
[2]
Analog input 54
[7]
Pulse input 29
[8]
Pulse input 33
[20] Digital pot.meter
[21] Analog input X30/11 (General Purpose I/O Option Module)
[22] Analog input X30/12 (General Purpose I/O Option Module)
[23] Analog Input X42/1
[24] Analog Input X42/3
[25] Analog Input X42/5
[29] Analog Input X48/2
[30] Ext. Closed Loop 1
[31] Ext. Closed Loop 2
[32] Ext. Closed Loop 3
3-16 Reference 2 Source
Option:
[0]
No function
[1]
Analog input 53
[2]
Analog input 54
[7]
Pulse input 29
[8]
Pulse input 33
[20] Digital pot.meter
[21] Analog input X30/11
[22] Analog input X30/12
[23] Analog Input X42/1
[24] Analog Input X42/3
[25] Analog Input X42/5
[29] Analog Input X48/2
[30] Ext. Closed Loop 1
[31] Ext. Closed Loop 2
[32] Ext. Closed Loop 3
®
is a registered Danfoss trademark
Function:
3-15 Reference 1 Source, 3-16 Reference
2 Source and 3-17 Reference 3 Source
define up to 3 different reference
signals. The sum of these reference
signals defines the actual reference.
Function:
Select the reference input to be used
for the second reference signal.
3-15 Reference 1 Source, 3-16 Reference
2 Source and 3-17 Reference 3 Source
define up to 3 different reference
signals. The sum of these reference
signals defines the actual reference.