Hart -Protocol; Hardware And Software Requirements - ABB Endura AZ series User Manual

Integral and remote transmitter, combustion oxygen monitor
Table of Contents

Advertisement

Endura AZ series integral and remote transmitter
Combustion oxygen monitor
®
7 HART
-Protocol
Endura AZ20 transmitters are HART-compatible, factory-calibrated devices. HART-Protocol enables
simultaneous indication of process variables and digital communication. The 4 to 20 mA current output
signal transmits process information and the digital signal is used for bi-directional communication. The
analog process value output enables analog indicators, recorders and controllers to be used, while the
simultaneous digital communication uses HART-Protocol.

7.1 Hardware and Software Requirements

Item
Device Manager
(Hardware)
Compatible
Management Software
Hand-held Terminal
Device Type Manager
(Software)
DTM
Electronic Device
Description (Software)
EDD
Table 7.1 HART-Protocol – Hardware / Software Requirements
68
Description
Install a HART modem (FSK Frequency Shift Keyed-Modem) for
HART-Communication when connecting to a PC.
The HART-Modem converts the analog 4 to 20 mA signal into a digital
output signal (Bell Standard 202) and connects to the PC using a USB
(or RS232C) connector.
Alternatively, a hand-held terminal can be used (see below).
Management
HART-compatible devices using 'Universal' and 'Common Practice'
commands.
The transmitter can be accessed and configured using a compatible
hand-held terminal (such as the ABB Mobility DHH801-MFC or
equivalent – see Fig. 7.1, page 69).
Transmitter connection is made in parallel with the 4 to 20 mA current
output – see Section 4.8, page 21, Current Output (4 to 20 mA) for
terminal connection details.
Provides offline and online configuration of the transmitter.
Provides online monitoring and simulation of inputs and diagnostics.
Compatible with FDT frameworks, for example: ABB Asset Vision
Basic (DAT200).
Provides offline and online configuration of the transmitter.
Provides online monitoring and simulation of inputs and diagnostics.
Compatible with Emerson AMS and Siemens PDM tools.