Hart Common Practice Command Set - ABB Endura AZ series User Manual

Integral and remote transmitter, combustion oxygen monitor
Table of Contents

Advertisement

Endura AZ series integral and remote transmitter
Combustion oxygen monitor

7.4 HART Common Practice Command Set

Command
Description
No.
33
Read Transmitter
Variables
34
Write Primary Variable
Damping Value
35
Write Primary Variable
Range Values
38
Reset Configuration
Changed Flag
40
Enter / Exit Primary
Variable Current Mode
Table 7.3 Common Practice Command Set
72
Details
Up to 4 slots. Each slot can be programmed to return the
following parameters based on the Transmitter Variable
Code:
0 = % Oxygen
1 = Cell temperature
2 = Cell mV
3 = Cold junction
4 = Heater power (%)
5 = Rate of rise of cell temperature
6 = Cell impedance
7 = Cell impedance drift
8 = Recovery rate
9 = Test gas response time
10 = O
deviation
2
11 = Cell calibration offset
12 = Cell calibration factor
13 = Cell zero offset
14 = Mains frequency
15 = Mains voltage
Sets the filter value for the % Oxygen reading.
Sets the % Oxygen range hi and lo values.
Bit 6 (Configuration Changed) of the Transmitter Status Byte
is reset by this command.
When a parameter has been changed via HART or the local
HMI the configuration changed bit is set.
For system troubleshooting purposes, current output 1 can
be set to a constant mA value.
Entering a value of 0 mA cancels the fixed output mode.