Simulation - E - ACS contsys Sonicont USN4SP Technical Manual

Ultrasonic level transmitter / level switch non-contact measurement of filling levels in liquids, pastes and coarse bulk materials
Table of Contents

Advertisement

5 .8 Simulation – E
The symbol E at a menu item indicates its position in the extended menu structure.
This extended menu structure can be shown in the submenu display by the menu item menu
structure.
5 .8 .1 Output
5 .8 .1 .1 Switch Output S1/S2/S3/S4
The switch output is activated resp. deactivated regardless of an already existing activation and also
regardless of delay times.
5 .8 .1 .2 Signal Output
At the signal output an analogue signal is output regardless of the current measuring value.
The input range is limited, dependent on the set Operating Mode.
3.600 – 22.00 mA (4-20 mA)
– 22.00 mA (0-20 mA)
– 11.00 V (0-10 V)
5 .8 .2 Display Value
The display value can be simulated, whereby all following functional steps (signal output, switch
output) are also simulated acc. to the settings.
The input range is limited to the set measuring range.
ACS-CONTROL-SYSTEM GmbH l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l info@acs-controlsystem.de