Basic Setting - ACS contsys Sonicont USN4SP Technical Manual

Ultrasonic level transmitter / level switch non-contact measurement of filling levels in liquids, pastes and coarse bulk materials
Table of Contents

Advertisement

5 .6 Basic setting

The symbol E at a menu item indicates its position in the extended menu structure.
This extended menu structure can be shown in the submenu display by the menu item menu
structure.
5 .6 .1 Measure conditions
Preselection for optimized adaption at increased requirements.
Usage
Object detection
o
Each measuring value at the set pulse rate will be displayed resp. output.
Fluid
o
The measured signal will be checked for plausibility and fast signal changes > 1m/min,
e.g. due to an agitator, will be suppressed.
If faster signal changes occurs, e.g. at filling or emptying, this can be allowed separately
(menu "Fast change rate")
Bulk Solid
o
The measured signal will be checked for plausibility and fast signal changes > 1m/min,
e.g. due to an agitator, will be suppressed.
If faster signal changes occurs, e.g. at filling or emptying, this can be allowed separately
(menu "Fast change rate")
Default > Fluid