Analog value processing
C.3 Representation of input ranges
Table C- 14
Resistance-type thermometer Ni 100 Climate
Ni 100 Climate in °C
Values
(1 digit = 0.01 °C)
dec.
> 155.00
32767
155.00
15500
:
:
130.01
13001
130.00
13000
:
:
-60.00
-6000
-60.01
-6001
:
:
-105.00
-10500
< - 105.00
-32768
C.3.4

Measured values for wire break diagnostics

Measured values for "Wire break" diagnostics as a function of diagnostics enables
With suitable parameter assignment, events that occur trigger a diagnostics entry and a
diagnostics interrupt.
Table C- 15
Measured values for wire break diagnostics
Format
Parameter assignment
S7
"Wire break" diagnostics enabled
"Overflow/Underflow" diagnostics
enabled or disabled
("Wire break" diagnostics has a higher
priority than "Overflow/Underflow" diag-
nostics)
"Wire break" diagnostics disabled
"Overflow/Underflow" diagnostics
enabled
"Wire break" diagnostics disabled
"Overflow/Underflow" diagnostics
disabled
202
Ni 100 Climate in
°F
hex.
(1 digit = 0.01 °F)
7FFF
> 311.00
3C8C
311.00
:
:
32C9
266.01
32C8
266.00
:
:
E890
-76.00
E88F
-76.01
:
:
D6FC
-157.00
8000
< - 157.00
Measured values
32767
-32767
-32767
Values
dec.
hex.
32767
7FFF
31100
797C
:
:
26601
67E9
26600
67E8
:
:
-7600
E250
-7601
E24F
:
:
-15700
C2AC
-32768
8000
Explanation
7FFF
"Wire break" or "Cable break" diagnostics
H
alarm
8000
Measured value after leaving the under-
H
range
Diagnostics alarm "Low limit" violated
8000
Measured value after leaving the underrange
H
CPU 1512C-1 PN (6ES7512-1CK01-0AB0)
Range
Overflow
Overrange
Nominal range
Underrange
Underflow
Manual, 12/2017, A5E40898741-AA