Table C- 12
Resistance-type thermometer Pt 100 Climate
Pt 100 Climate/
Values
in °C
dec.
(1 digit = 0.01 °C)
> 155.00
32767
155.00
15500
:
:
130.01
13001
130.00
13000
:
:
-120.00
-12000
-120.01
-12001
:
:
-145.00
-14500
< -145.00
-32768
Table C- 13
Resistance-type thermometer Ni 100 standard
Ni 100
Values
Standard
dec.
hex.
in °C
(1 digit =
0.1 °C)
> 295.0
32767
7FFF
295.0
2950
B86
:
:
:
250.1
2501
9C5
250.0
2500
9C4
:
:
:
-60.0
-600
FDA8
-60.1
-601
FDA7
:
:
:
-105.0
-1050
FBE6
< -105.0
-32768
8000
CPU 1512C-1 PN (6ES7512-1CK01-0AB0)
Manual, 12/2017, A5E40898741-AA
Pt 100 Climate/
in °F
hex.
(1 digit = 0.01 °F)
7FFF
> 311.00
3C8C
311.00
:
:
32C9
266.01
32C8
266.00
:
:
D120
-184.00
D11F
-184.01
:
:
C75C
-229.00
8000
< -229.00
Ni 100
Values
Standard
dec.
hex.
in °F
(1 digit =
0.1 °F)
> 563.0
32767
7FFF
563.0
5630
15FE
:
:
:
482.1
4821
12D5
482.0
4820
12D4
:
:
:
-76.0
-760
FD08
-76.1
-761
FD07
:
:
:
-157.0
-1570
F9DE
< -157.0
-32768
8000
Analog value processing
C.3 Representation of input ranges
Values
dec.
hex.
32767
7FFF
31100
797C
:
:
26601
67E9
26600
67E8
:
:
-18400
B820
-18401
B81F
:
:
-22900
A68C
-32768
8000
Ni 100
Values
Standard
dec.
hex.
in K
(1 digit =
0.1 K)
> 568.2
32767
7FFF
568.2
5682
1632
:
:
:
523.3
5233
1471
523.2
5232
1470
:
:
:
213.2
2132
854
213.1
2131
853
:
:
:
168.2
1682
692
< 168.2
32768
8000
Range
Overflow
Overrange
Nominal range
Underrange
Underflow
Range
Overflow
Overrange
Nominal range
Underrange
Underflow