Parameter data records
B.3 Structure of a data record for output channels of the analog on-board I/O
Codes for output ranges
The following table contains all output ranges for voltage and current of the outputs of the
analog on-board I/O with the corresponding codes. You must enter these codes in each case
in byte 3 of the corresponding data record (see previous figure).
Table B- 9
Output range for voltage
1 to 5 V
0 to 10 V
±10 V
Output range for current
0 to 20 mA
4 to 20 mA
±20 mA
Permitted substitute values
The following table lists all output ranges for the permitted substitute values. You must enter
these substitute values in each case in bytes 6 and 7 of the data record for the
corresponding channel (see the previous figure). You can find the binary representation of
the output ranges in the section Representation of output ranges (Page 203).
Table B- 10
Output range
±10 V
1 to 5 V
0 to 10 V
±20 mA
4 to 20 mA
0 to 20 mA
174
Codes for output range
Permitted substitute value for the output range
Code
0000 0011
0000 0010
0000 0000
Code
0000 0001
0000 0010
0000 0000
Permitted substitute value
-32512 ... +32511
-6912 ... +32511
0 ... +32511
-32512 ... +32511
-6912 ... +32511
0 ... +32511
CPU 1512C-1 PN (6ES7512-1CK01-0AB0)