Hardware interrupt limits
The values that can be set for hardware interrupts (high/low limit) must be within the nominal
range and overrange/underrange of the relevant measuring range.
The following tables list the permitted hardware interrupt limits. The limits depend on the
selected measurement type and measuring range.
Table B- 4
Voltage
±5 V, ±10 V
32510
-32511
Table B- 5
Current
±20 mA
32510
-32511
Table B- 6
Thermal resistor
9999
-2429
Table B- 7
Thermal resistor
2949
-1049
CPU 1512C-1 PN (6ES7512-1CK01-0AB0)
Manual, 12/2017, A5E40898741-AA
B.2 Structure of a data record for input channels of the analog on-board I/O
Voltage limits
Current and resistance limits
4 to 20 mA /
0 to 20 mA
32510
-4863
Limits for thermal resistor Pt 100 Standard and Pt 100 Climate
Pt 100 Standard
°C
°F
K
18319
12731
-4053
303
Limits for thermal resistor Ni 100 Standard and Ni 100 Climate
Ni 100 Standard
°C
°F
K
5629
5681
-1569
1683
1 to 5 V, 0 to 10 V
32510
-4863
Resistance
(all configurable measuring ranges)
32510
1
Pt 100 Climate
°C
°F
15499
31099
-14499
-22899
Ni 100 Climate
°C
°F
15499
31099
-10499
-15699
Parameter data records
High limit
Low limit
High limit
Low limit
K
---
High limit
---
Low limit
K
---
High limit
---
Low limit