• For supply cables larger than AWG8: use maximum allowed ampacity of the selected
supply cables and compare with value in table below (see CEC Part 1 table 17)
< 100 A: use AWG8
< 200 A: use AWG6
< 300 A: use AWG4
Always check the voltage drop over the cable (less than 5 % of the nominal voltage is
recommended).
Example of supply cable calculation: I
recommended fuse = 40 A
• Single supply cables (3 phases + 1 PE - configuration (1)):
• I = 28 A + 25 % = 28 x 1.25 = 35 A
• For AWG8, the maximum current at 40 °C is 50 A x 0.88 = 44 A, which is sufficient =>
use AWG8.
• Install the prescribed maximum fuse (40 A) on each cable
• Parallel supply cable (2 x 3 phases + 2 PE - configuration (2)):
• I = (28 A + 25%)/2 = (28 x 1.25)/2 = 17.5 A
• For a AWG14, the maximum current at 40 °C is 20 A x 0.88 x 0.8 = 14.1 A, which is
insufficient. For an AWG14, the maximum current is 25 x 0.88 x 0.8 = 17.6 A. So 2
parallel cables of 3 x AWG12 + 2 x AWG12 are sufficient.
• Install 20 A fuses on each cable.