sauter EQJW145 Operating Manual

sauter EQJW145 Operating Manual

Heating controller
Table of Contents

Advertisement

R
EQJW145: Heating
controller
Operating manual
7010015003 A

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the EQJW145 and is the answer not in the manual?

Questions and answers

Summary of Contents for sauter EQJW145

  • Page 1 EQJW145: Heating controller Operating manual 7010015003 A...
  • Page 2 7010015003 A Printed in Switzerland Subject to changes © Fr. Sauter AG Im Surinam 55 CH - 4016 Basel www.sauter-controls.com 7010015003 A © Fr. Sauter AG...
  • Page 3: Table Of Contents

    EQJW145: Heating controller Table of contents Table of contents Table of contents ......................3 Symbols used in this manual ..................7 General information .................... 9 Introduction....................9 Safety information ..................9 Description of the operating controls ............. 11 Front view of the EQJW 145 ..............11 Top Rotary switches (heating) ..............
  • Page 4 EQJW145: Heating controller Table of contents 4.1.2 Displays when back-up mode, reduced mode and normal mode are set50 Entering the setpoint temperature in normal mode......... 51 Enter setpoint temperature in reduced mode.......... 52 Weekly switching programme for heating ..........52 4.4.1...
  • Page 5 EQJW145: Heating controller Table of contents 6.2.1 Assigning addresses ................67 6.2.2 Room operating unit EDB 100 ..............68 6.2.3 Sending and receiving outdoor temperatures ......... 68 6.2.4 Requesting and processing a heat requirement ........68 6.2.5 Requesting and processing a return temperature ........68 6.2.6...
  • Page 6 EQJW145: Heating controller Table of contents 15.2 List of communication parameters ............102 15.3 Weekly switching programme: heating ..........103 15.4 Calendar switching programme: heating ..........103 15.5 Weekly switching programme: domestic hot water....... 104 15.6 Weekly switching programme: pilot timer/circulating pump ....104 Table of Figures ......................
  • Page 7: Symbols Used In This Manual

    EQJW145: Heating controller Symbols used in this manual Symbols used in this manual Information Information concerning the use of the product. Warnings Factory setting of the EQJW 145 (e.g. manufacturer's specified control values, switching times, etc.) The operating instructions explain the various functions of the device, step by...
  • Page 8 EQJW145: Heating controller Symbols used in this manual 7010015003 A © Fr. Sauter AG...
  • Page 9: General Information

    EQJW145: Heating controller General information General information Introduction Congratulations! You have chosen a Sauter heating controller. The equitherm EQJW 145 is a quality product from one of the leading manufacturers of control technology products for the heating, ventilation and air conditioning industry.
  • Page 10 EQJW145: Heating controller General information 7010015003 A © Fr. Sauter AG...
  • Page 11: Description Of The Operating Controls

    EQJW145: Heating controller Description of the operating controls Description of the operating controls Front view of the EQJW 145 °C Fig. 1: EQJW 145 - Front view Rotary switch Display ESC button Input knob The device has a rotary switch with 10 positions, an input knob and a button.
  • Page 12: Top Rotary Switches (Heating)

    EQJW145: Heating controller Description of the operating controls Top Rotary switches (heating) The switch positions have these meanings: Operating modes: Inputs: Automatic mode according Setpoint adjustment to switching programme Normal mode Regulator is Setpoint adjustment continuously in Reduced mode normal mode...
  • Page 13: Input Knob

    EQJW145: Heating controller Description of the operating controls Input knob You can use the input knob to scroll through menus, and to select or change values. Unless explicitly described otherwise, you can scroll through or change menus/values in a ring structure. There is no 'limit stop' for adjusting values or scrolling.
  • Page 14 EQJW145: Heating controller Description of the operating controls Display of outdoor temperature Display of room temperature Display of return temperature Display of tank temperature Controller is in summer mode Calendar switching programme mode is currently active Domestic hot water. flashing: with increased temperature...
  • Page 15: Commissioning

    EQJW145: Heating controller Commissioning Commissioning Operating the device for the first time When you operate the equitherm EQJW 145 for the first time, you must set the date and time. Essentially, once this is done, the controller is ready for use.
  • Page 16: Setting The Date

    EQJW145: Heating controller Commissioning 3.1.2 Setting the date To enable you to set the date, you must first move the bottom rotary switch into one of the following positions (see 4.1): Off mode Continuous heating to normal DHW temperature Continuous heating to increased DHW temperature Automatic mode Set the top rotary switch to automatic mode.
  • Page 17: List Of Service Parameters

    EQJW145: Heating controller Commissioning 3.2.1 List of SERVice parameters The following SERVice parameters can be reached on commissioning level. Para- Description Range Step value meter SP01 Software version Y.XX (read only) SP06 Control model 0...3 1 = one control valve on the primary side...
  • Page 18: Access To Commissioning Level

    EQJW145: Heating controller Commissioning 3.2.2 Access to commissioning level Set the upper rotary switch to the Service position. Press the input knob, select 'In' (= commissioning). Press the input knob. Turn the input knob, show the code. Press the input knob.
  • Page 19: Service Level

    EQJW145: Heating controller Commissioning Turn the input knob. Select the SERVice parameter you want. Press the input knob. • The value of the parameter is shown. Turn the input knob. • The value of the parameter is changed. Press the input knob.
  • Page 20: View Service Parameters

    EQJW145: Heating controller Commissioning 3.3.2 View SERVice parameters Turn the input knob. Select the SERVice parameter you want. Press the input knob. • The value of the parameter is shown. To leave the value unchanged, press ESC to exit the display.
  • Page 21: List Of Service Parameters

    EQJW145: Heating controller Commissioning 3.3.4 List of SERVice parameters Parameter Description Range Step value SP01 Software version Y.XX (read only) SP02 Device status (error coding) (read only) SP03 View logbook SP04 Software reset 0...3 0 = no Reset 1 = factory setting for SE + CO parameters...
  • Page 22 EQJW145: Heating controller Commissioning Parameter Description Range Step value Correction to outdoor temperature T A in K SP12 -10.0…+10.0 SP13 Return temperature recording 0…1 0 = return temperature is not recorded 1 = return temperature is recorded Correction to return temperature T RF (MOD3: T RF of heating circuit) SP14 -10.0…+10.0...
  • Page 23 EQJW145: Heating controller Commissioning Parameter Description Range Step value SP34 Functions for DHW 0…4 0 = not enabled. 1 = MOD 1, 2: with sep. charge pump using one DHW sensor 2 = MOD 1, 2: with sep. charge pump using two...
  • Page 24: Tab. 2: Service Parameter

    EQJW145: Heating controller Commissioning Parameter Description Range Step value SP49 Configurable output 0…5 0 = no function 1 = pilot timer function 2 = 2nd tank charge pump (MOD1, 2 only) 3 = forced control of heating medium pump at low...
  • Page 25: Explanations For Individual Service Parameters

    EQJW145: Heating controller Commissioning 3.3.5 Explanations for individual SERVice parameters View software version SP01 The controller's software version number is shown. View device status SP02 SERVice parameter 2 allows you to read the device status of the EQJW 145. Value 0 means that the EQJW 145 is operating without faults. The coding for faults is shown in section7.1.2.
  • Page 26 Room operating unit EGS52/15 allows you to switch over the controller's mode remotely. Room operating unit EDB100 can also be connected via the device bus and used to switch the mode over. The mode on the EQJW145 can also be changed using a control station via Modbus. In case of contradictory commands, the following priority applies: direct settings on EQJW145 have priority 1.
  • Page 27 EQJW145: Heating controller Commissioning the EQJW 145. This, in turn, means that the flow temperature and, therefore, the heating capacity, for the room are altered accordingly. Connect room temperature SP09 A room temperature sensor (resistance sensor or device bus) is required for this function.
  • Page 28 EQJW145: Heating controller Commissioning Return temperature recording SP13 If a return temperature sensor is to be used, this parameter must be set to 1. Correction to return temperature SP14 The measured value for the return temperature is calibrated with the help of this SERVice parameter.
  • Page 29: Fig. 4: Limitation Function

    EQJW145: Heating controller Commissioning R F m ax . L 0 (R F ) L 0B W (R F ) L U (R F ) A (R F) B 1 09 8 0 Fig. 4: Limitation function The following parameters are available to set the limiting function:...
  • Page 30 35 kWh / h x 1200 pulses / kWh = 42,000 pulses / h. This gives a value that must be entered on the EQJW145 of 42,000 pulses / h = 42,000 : 60 pulses / min = 700 pulses / min. The second limit value is 50 kW.
  • Page 31: Tab. 3: Dhw Preparation

    EQJW145: Heating controller Commissioning A limit value of between 16 and 60 pulses / minute cannot be entered because the measurement accuracy required for control is no longer available in this range. If a value in the range from 60 to 16,000 has been...
  • Page 32 EQJW145: Heating controller Commissioning Maximum permitted DHW temperature SP35 This SERVice parameter is used to impose an upper limit on the temperature for domestic hot water, which can be set with the lower rotary switch. If the rotary knob used to set the values is turned further to the right (increase values) although the upper limit value has already been reached, the display will automatically show the lowest value, which is increased again.
  • Page 33: Fig. 5: Guideline For The Slope Of The Heating Characteristic

    When heat from another device is requested via the device bus, SP42 can be used to make the EQJW145 control to a setpoint that is higher by the amount entered for SP42 (0K to 30K) than the amount actually requested by the other device.
  • Page 34 EQJW145: Heating controller Commissioning Outdoor temperature recording for heating limit SP45 You can select whether the EQJW 145 should use the current measured outdoor temperature or the averaged outdoor temperature over the last 21 hours for the heating limit (see SP44). If the outdoor temperature averaged...
  • Page 35 EQJW145: Heating controller Commissioning 2 = 2nd tank charge pump (only MOD1, 2) The 2nd tank charge pump is switched on if the actual value for the flow temperature is greater than the setpoint temperature for the DHW for start of heating + setpoint boost DHW (see SP38).
  • Page 36 EQJW145: Heating controller Commissioning Optimisation SP53 When the optimisation function (SP53 = 1) is enabled, it has the effect that the selected room temperature is actually reached in normal mode at the point in time that was set in the switching programme. The usage times should therefore be set as they are actually needed.
  • Page 37 EQJW145: Heating controller Commissioning When the optimisation function is switched off (SP53 = 0), the heating is also switched off initially on changing from normal to reduced mode if the room temperature is at least 2.5 K higher than the setpoint for reduced mode. Not until the room temperature has fallen back to the setpoint does the heating mode start again in accordance with the heating characteristic.
  • Page 38: Communication Level

    EQJW145: Heating controller Commissioning If ready-for-laying heating is activated, the current phase appears: 1 = Initialisation 2 = Rising-temperature phase 3 = Temperature-maintenance phase, 4 = Falling-temperature phase Once the floor drying has been successfully completed, the numerical value of 9 appears. If the floor drying function was disrupted (due to a sensor failure or a long-lasting high control offset etc.), value 8 is shown instead of 9...
  • Page 39: Access To Communication Level

    EQJW145: Heating controller Commissioning 3.4.1 Access to communication level Set top rotary switch to Service position. Turn the input knob. Select 'CO' (Communication). Press the input knob. Turn the input knob. Show the code. Press the input knob. • The first communication parameter is shown.
  • Page 40: List Of Communication Parameters

    EQJW145: Heating controller Commissioning 3.4.4 List of communication parameters Parameter Description Range Step- value CP01 Internal serial number of EQJW 145 (read only) – CP02 Type of communication 0…5 0 = no communication 1 = device bus 2 = MOD bus via RS485...
  • Page 41: Tab. 4: Communication Parameters

    EQJW145: Heating controller Commissioning Parameter Description Range Step- value CP19 – Device bus: address of EDB 100 digital room operating unit auto, 2…32 CP20 SMS or MOD bus via modem: automatic configuration of modem 0…1 0 = not enabled. 1 = enabled...
  • Page 42: Explanations Of Individual Communication Parameters

    EQJW145: Heating controller Commissioning 3.4.5 Explanations of individual communication parameters Serial number CP01 The serial number of the EQJW 145 is shown. Type of communication CP02 The type of communication can be set. You can choose from these options: 0 = no communication...
  • Page 43 EQJW145: Heating controller Commissioning Device bus: time synchronisation CP09 If CP 09 is set to 1, this controller sends time information on the device bus every 24 hours. All devices with CP 09 set to 0 will evaluate this information and set their clocks accordingly.
  • Page 44 EQJW145: Heating controller Commissioning Device bus: EDB 100 digital room operating unit CP18 If an EDB100 digital room operating unit is to be used, CP18 must be set to If an EDB 100 digital room operating unit is used, the actual value for the room temperature is evaluated by the EDB 100.
  • Page 45 EQJW145: Heating controller Commissioning Modbus via RS485 or Modbus via modem: control station commands expire CP27 after the control station has been inactive for 30 minutes When CP27 = 1: if the controller is no longer receiving any Modbus enquiries, operating statuses specified via Modbus become invalid after 30 minutes and the controller operates independently of the control station again.
  • Page 46 EQJW145: Heating controller Commissioning 7010015003 A © Fr. Sauter AG...
  • Page 47: Operation

    EQJW145: Heating controller Operation Operation Operating modes The top rotary switch is used to set the heating circuit. The five left-hand positions of the top rotary switch (see 2.1 ) enable you to select one of the following modes: Manual mode – outputs for pump and valve can be controlled manually Back-up mode –...
  • Page 48: Displays When Automatic Mode Is Set

    EQJW145: Heating controller Operation Continuous heating to increased DHW temperature – tank is kept at increased DHW temperature Automatic mode – hot water preparation automatically changes the mode according to the weekly programme that has been set. Automatic mode should be selected in normal cases.
  • Page 49 EQJW145: Heating controller Operation The current actual value for the room temperature (only if a room sensor is present). • The flow setpoint (not available in OFF mode or summer mode, for example). • The current actual value for the flow temperature.
  • Page 50: Displays When Back-Up Mode, Reduced Mode And Normal Mode Are Set50

    EQJW145: Heating controller Operation 4.1.2 Displays when back-up mode, reduced mode and normal mode are set To show the various displays described below, the bottom rotary switch must be moved to one of the following positions (see 4.1). Off mode...
  • Page 51: Entering The Setpoint Temperature In Normal Mode

    EQJW145: Heating controller Operation You can also turn the knob in the opposite direction to scroll backwards through the displays. In some cases, more displays can be added to the display loop, e.g. Show setpoint and actual value for return temperature The display (see 7), can be added in case of a fault A display of the connection status can be added for modem operation (see 6.4)
  • Page 52: Enter Setpoint Temperature In Reduced Mode

    EQJW145: Heating controller Operation Enter setpoint temperature in reduced mode To enter setpoints, the bottom rotary switch must be moved to one of the following positions (see 4.1). Off mode Continuous heating to normal DHW temperature Continuous heating to increased DHW temperature...
  • Page 53: Calling Up The Weekly Switching Programme

    EQJW145: Heating controller Operation The factory setting for the weekly programme is: Time Mode Daily 06:00 Normal mode Daily 22:00 Reduced mode You are recommended to note any change to the weekly switching programme in the relevant table in Section 14. Before you can call up, view or edit the weekly switching programme, you must check whether the bottom rotary switch is in one of these positions (see 4.1).
  • Page 54: Enter A Switching Command

    EQJW145: Heating controller Operation 4.4.3 Enter a switching command Turn the input knob until you reach the next empty switching command. Push the input knob. • The new switching command is shown. Turn the input knob. • The time for the switching command is changed.
  • Page 55: Calendar Switching Programme

    EQJW145: Heating controller Operation Calendar switching programme 4.5.1 Calling up the calendar switching programme The calendar programme can influence the automatic mode of the heating circuit over longer periods, in addition to the weekly programme. The calendar switching programme specifies date periods (e.g. for holidays) when the weekly switching programme is only enabled up to a defined mode.
  • Page 56: Enter A Switching Command

    EQJW145: Heating controller Operation 4.5.3 Enter a switching command Turn the input knob until you reach the next empty switching command. Push the input knob. • The new switching command is shown. Turn the input knob. • The date for the switching command is changed.
  • Page 57: Temporary Temperature Change For The Heating Circuit

    EQJW145: Heating controller Operation Temporary temperature change for the heating circuit Before a temporary temperature change for the heating circuit can be implemented, ensure that the bottom rotary switch is in one of these positions (see 4.1). Off mode Continuous heating to normal DHW temperature...
  • Page 58: Entering Dhw Temperatures

    EQJW145: Heating controller Operation Entering DHW temperatures To enter DHW temperatures, ensure that the top rotary switch is in one of these positions (see 4.1). Back-up mode Reduced mode Normal mode Automatic mode Procedure Set the bottom rotary switch to the 'Adjust setpoint for normal DHW temperature' position.
  • Page 59: Notes On The Boosted Dhw Temperature

    EQJW145: Heating controller Operation 4.7.1 Notes on the boosted DHW temperature The boosted DHW temperature is intended for thermal disinfection of hot water preparation. The higher temperature should destroy germs (legionella). To achieve this aim reliably, the return temperature limitation (see SP27) and power/flow limitation (see SP29ff) functions are not enabled with an increased DHW temperature.
  • Page 60: Calling Up The Weekly Switching Programme

    EQJW145: Heating controller Operation This means that the controller is set to normal hot water mode every night. This switching command may only be deleted if it is replaced by other switching commands . You are recommended to note any change to the weekly switching programme in the relevant table in section 15.
  • Page 61: Enter A Switching Command

    EQJW145: Heating controller Operation 4.8.3 Enter a switching command Turn the input knob until you reach the next empty switching command. Push the input knob. • The new switching command is shown. Turn the input knob. • The time for the switching command is changed.
  • Page 62: Weekly Switching Programme For Pilot Timer/Circulating Pump

    EQJW145: Heating controller Operation Weekly switching programme for pilot timer/circulating pump The weekly switching programme is repeated every week. It comprises up to 48 switching commands (six for each day and a further six for the whole week) with the associated operating modes, which can be entered in a 10- minute raster.
  • Page 63: Calling Up The Weekly Switching Programme

    EQJW145: Heating controller Operation 4.10 Calling up the weekly switching programme Set the bottom rotary switch to PROG Turn knob. Select day of the week (1=Monday, 2= Tuesday, 1 - 7 daily). In this example, 5 = Friday was chosen.
  • Page 64: Change/Delete Switching Command

    EQJW145: Heating controller Operation 4.10.3 Change/delete switching command As described in 'View switching command', proceed as follows: e.g.: Press knob. • Switching command is called up. Turn knob. Choose whether you want to delete (Clr) or change (SEt) the switching command.
  • Page 65: Manual Mode

    EQJW145: Heating controller Manual mode Manual mode In manual mode, the system can be controlled by hand during installation or in case of an incident. There is no control in manual mode. The output relays are opened or closed. The valve is opened or closed according to the specified values.
  • Page 66: Set Status Of Other Outputs (Pumps, Configurable Output) For Manual Mode

    EQJW145: Heating controller Manual mode Set status of other outputs (pumps, configurable output) for manual mode Turn the input knob. Select the output you want. (UP 1 = heating pump, LP = charge pump, rEL = configurable output). Press the input knob.
  • Page 67: Communication Functions

    EQJW145: Heating controller Communication functions Communication functions The EQJW 145 has a communication interface which can be used for the device bus, or alternatively for Modbus communication – also via modem. Fault messages can still be sent by modem to a mobile phone as SMS messages.
  • Page 68: Room Operating Unit Edb 100

    EQJW145: Heating controller Communication functions 6.2.2 Room operating unit EDB 100 Using the EDB 100 room operating unit, the setpoint temperatures can be adjusted, various measured values can be interrogated and the mode can be switched over. These functions can be carried out from the living room. To...
  • Page 69: Modbus Communication

    EQJW145: Heating controller Communication functions Modbus communication The EQJW 145 can respond to enquiries in the Modbus RTU protocol as a slave. For this purpose, an RS-485 two-wire bus is connected to terminals 18 and 19. A suitable Modbus master (BMS centre) can send enquiries or commands via this bus.
  • Page 70: Modbus Data Points (Holding Register)

    EQJW145: Heating controller Communication functions The EQJW 145 is compatible with the 'Modbus-Frame' protocol extension. Enquiries in standard format are answered in standard format, and frame enquiries receive an answer in frame format. This format allows reliable data transmission even if the data are segmented during transmission. For Modbus...
  • Page 71 EQJW145: Heating controller Communication functions Number of Description Comment Read Decimal Units With math. holding only points Sign? register 40108 Mode_Rk2 1=Auto, 2=Stdby, 3=Manual, 4=Sun, 5=Moon 40109 ControlSignal_Rk2 Opening for control signal Rk2 [0...100%] Value T A heating switch-off 40117 AT_HeatOff_Rk1 °C...
  • Page 72: Tab. 6: Modbus Data Points

    EQJW145: Heating controller Communication functions Number of Description Comment Read Decimal Units With math. holding only points Sign? register 42000 to Switching command, 1 48 possible switching commands for the 42047 heating circuit heating circuit 42100 to Switching command, 2...
  • Page 73 EQJW145: Heating controller Communication functions For the other control loops or the program for the pilot timer/circulation pump, the same logic applies, but the register numbers are 100 higher in each case. Every possible switching command has its own holding register (a 16-bit value) that can be read or written.
  • Page 74: Modbus Data Points (Coils)

    EQJW145: Heating controller Communication functions 6.3.2 Modbus data points (coils) Coil no. Description Comment Can be Can be set? deleted? Collective level bit Controller controls all functions AUTONO independently of the control station MOUS Binary input, Cl. 22 Binary input, Cl. 22/Cl. 21...
  • Page 75: Modem Operation

    EQJW145: Heating controller Communication functions Coil no. Description Comment Can be Can be set? deleted? Timeout BMS BMS monitoring INACTIV ACTIVE Tab. 8: Modbus data points coils When a function of the controller is specified via Modbus (e.g. status of the...
  • Page 76: Sending Sms If There Is A Fault On The Installation

    EQJW145: Heating controller Communication functions 6.4.3 Sending SMS if there is a fault on the installation A modem enables the controller to send an error message to a mobile phone. As soon as a fault is registered in the device status register of the controller, an SMS message is sent.
  • Page 77: Setting Parameters Using The Pc

    EQJW145: Heating controller Communication functions Display Meaning EndE The connection is being disconnected It was impossible to reach the provider or the control station with the permitted number of dialling attempts (new dialling attempts will be made on the next day) Tab.
  • Page 78 EQJW145: Heating controller Communication functions 7010015003 A © Fr. Sauter AG...
  • Page 79: Faults

    EQJW145: Heating controller Faults Faults Before you call a heating specialist, check: electrical fuses, main installation switch, burner function, heat medium pump, valve, fault display, time and day of the week for the EQJW 145. Displaying faults An operating fault is shown on the display by the flashing fault symbol (see section 2.5).
  • Page 80: Logbook

    EQJW145: Heating controller Faults The coding is as follows:- Err 1 (Sensor failure T F ) Err 2 (Sensor failure T A ) Err 3 (Sensor failure T R ) Err 4 (Sensor failure T RF ) Err 5 (Sensor failure T W2 ,T RF2 )
  • Page 81: Reset Functions

    EQJW145: Heating controller Faults The same symbols are used for the control offset or the limit violations that are also used in the normal display of the measured values (radiators etc.). By turning the knob, you can change between the display of the recorded setpoint and the excessively-deviating actual value.
  • Page 82 EQJW145: Heating controller Faults 7010015003 A © Fr. Sauter AG...
  • Page 83: Using The Controller

    EQJW145: Heating controller Using the controller Using the controller General information The EQJW 145 controller is used for weather-compensated flow temperature control of a heating circuit. An additional room temperature connection is possible. The controller changes the operating status in accordance with the switching commands that are entered, on a time-dependent basis.
  • Page 84: Control Model 1

    EQJW145: Heating controller Using the controller 8.2.1 Control model 1 Fig. 7: EQJW 145 Control model 1 Weather-compensating control of the flow temperature (secondary) in converter installations with DHW preparation (parallel circuit) with 2 charge pumps, via an additional converter (tank charge system) Main SERVice parameters (see also 3.3)
  • Page 85: Fig. 8: Eqjw 145 Control Model 1

    EQJW145: Heating controller Using the controller Fig. 8: EQJW 145 control model 1 Weather-compensating flow temperature control (secondary) in converter installations with priority DHW switching via diverter valve. Main SERVice parameters (see also 3.3) SP06 (Control model SP13 (Return temperature recording enabled) SP20 (Runtime for the 2nd final control element, i.e.
  • Page 86: Fig. 9: Eqjw 145 Control Model 1

    EQJW145: Heating controller Using the controller Fig. 9: EQJW 145 control model 1 Weather-compensating flow temperature control (secondary) in converter installations with DHW preparation using 2 charge pumps via an additional converter, and controller of the heating temperature for the DHW (tank charge system) Main SERVice parameters (see also 3.3):...
  • Page 87: Control Model 2

    EQJW145: Heating controller Using the controller 8.2.2 Control model 2 Fig. 10: EQJW 145 control model 2 Weather-compensating flow temperature control and DHW preparation via a mixer valve Main SERVice parameters (see also 3.3): SP06 (Control model) SP08 (Connect room operating unit EGS52/15 with room...
  • Page 88: Control Model 3

    EQJW145: Heating controller Using the controller 8.2.3 Control model 3 SP 49 Fig. 11: EQJW 145 control model 3 Weather-compensating flow temperature control (secondary) and separate fixed value control (secondary) for DHW preparation in converter installations Main SERVice parameters (see also 3.3):...
  • Page 89: Economy Tips

    EQJW145: Heating controller Economy tips Economy tips Heating is by far the largest consumer of energy in the household. 78 % of the energy required in a household is consumed by the heating (source: 'Wohnen & Energie Sparen/Living and Saving Energy'. BINE Information Service of the Karlsruhe Technical Information Centre.
  • Page 90 EQJW145: Heating controller Economy tips 7010015003 A © Fr. Sauter AG...
  • Page 91: Resistance Values For The Ni1000 Sensors

    EQJW145: Heating controller Resistance values for the Ni1000 sensors Resistance values for the Ni1000 sensors The temperature sensors required depending on the use of the EQJW 125 must conform to DIN 43760. Temperature (°C) Resistance value ( ) Ni1000 1549...
  • Page 92 EQJW145: Heating controller Resistance values for the Ni1000 sensors 7010015003 A © Fr. Sauter AG...
  • Page 93: Accessories

    EQJW145: Heating controller Accessories Accessories See the Sauter PDS for more components. Wiring diagram MOD 1, 2 EGS 52/15 EGT 333 EGS 52/15 EGT 333 MOD 3 Fig. 13: Wiring diagram Dimension drawing Fig. 14: Dimension drawing of EQJW 145 7010015003 A ©...
  • Page 94 EQJW145: Heating controller Dimension drawing 7010015003 A © Fr. Sauter AG...
  • Page 95: Technical Data

    EQJW145: Heating controller Technical data Technical data 14.1 Overview of technical data Power supply: 230 V ±15 %, 50…60 Hz Power supply tolerance: Power consumption: approx. 2 VA Type of protection: IP40 (when fitted in panels) (EN 60529) Protection class:...
  • Page 96: Tab. 12: Overview Of Technical Data

    EQJW145: Heating controller Technical data permitted start-up current 7A (max. 1sec) relay outputs for final control element 2 x normally open contacts, 230V/0.5A/cos > 0.5 Interface: electrical specification RS485, 2-wire. similar to RS232 Modbus (slave, format Modbus RTU, interface protocols...
  • Page 97: Overview Of Main Functions

    EQJW145: Heating controller Technical data 14.2 Overview of main functions The room temperature connection is enabled in the SERVice level. This Room temperature requires a room temperature sensor. The influence of the room temperature connection connection can be set in SERVice level. Maximum change to T...
  • Page 98 EQJW145: Heating controller Technical data The maximum flow or the maximum power can be limited. Limit values can Flow and power limitation be specified for the heating, DHW preparation and the combination of heating and DHW preparation. If the limit value is exceeded the flow temperature is reduced.
  • Page 99 EQJW145: Heating controller Technical data 3 weekly switching programmes with up to 48 switching commands and one Switching programmes calendar switching programme with up to 20 switching commands are available. The minimum switching interval is 10 minutes or 1 day. Modes from weekly and calendar switching programmes with lower energy consumption take priority.
  • Page 100 EQJW145: Heating controller Technical data 7010015003 A © Fr. Sauter AG...
  • Page 101: Overview Of Controller Settings

    EQJW145: Heating controller Overview of controller settings Overview of controller settings 15.1 List of SERVice parameters If the factory setting for the SERVice parameters is changed, the modified values must be entered in the table below. Parameter Parameter (change) SP01 X.xx...
  • Page 102: Tab. 14: List Of Communication Parameters

    EQJW145: Heating controller Overview of controller settings 15.2 List of communication parameters If the factory setting for the communication parameters is changed, the modified values must be entered in the table below. Parameter Parameter (change) CP01 CP15 CP02 CP16 CP03 19.200...
  • Page 103: Weekly Switching Programme: Heating

    EQJW145: Heating controller Overview of controller settings 15.3 Weekly switching programme: heating Time Mode (Deleted) Daily 06:00 Normal mode Daily 22:00 Reduced Mode Switching commands added for the weekly switching programme Time Mode ____________ ____________ ____________ ____________ ____________ ____________ ____________...
  • Page 104: Weekly Switching Programme: Domestic Hot Water

    EQJW145: Heating controller Overview of controller settings 15.5 Weekly switching programme: domestic hot water Time Mode (Deleted) Daily 06:00 Normal Mode Switching commands added for the weekly switching programme Time Mode ____________ ____________ ____________ ____________ ____________ ____________ ____________ ____________ ____________...
  • Page 105: Table Of Figures

    EQJW145: Heating controller Table of Figures Table of Figures Fig. 1: EQJW 145 - Front view ................... 11 Fig. 2: EQJW 145 - Top Rotary Switches..............12 Fig. 3: EQJW 145 - Bottom Rotary Switches ............. 12 Fig. 4: Limitation function.................... 29 Fig.
  • Page 106: List Of Tables

    EQJW145: Heating controller List of tables List of tables Tab. 1: SERVice parameter..................17 Tab. 2: SERVice parameter..................24 Tab. 3: DHW preparation.................... 31 Tab. 4: Communication parameters ................41 Tab. 5: statuses for domestic hot water..............59 Tab. 6: Modbus data points ..................72 Tab.
  • Page 107: Abbreviations

    EQJW145: Heating controller Abbreviations Abbreviations Abbreviations Term domestic hot water communication domestic hot water heating circuit pulse cold water control model SERVice SERVice parameter outdoor temperature flow temperature T Fi actual value for flow temperature T FS setpoint for flow temperature...
  • Page 108: Index

    EQJW145: Heating controller Index Index Abkürzungsverzeichnis ................107 Accessories....................93 Actuator....................... 28 Address....................... 67 After-run factor .................... 34 After-run time ....................32 Anti-frost....................34, 97 Automatic cut-off ..................98 Basic programme ..................9 Baud rate ....................42 Charge pump ....................32 Coil......................
  • Page 109 EQJW145: Heating controller Index Gerätestatus....................80 Heat requirement .................. 43, 68 Heaters ....................... 89 Heating characteristic.................. 33 Heating controller ..................9 Heating limit ..................33, 34, 96 Hilfskontakt ....................26 Holidays ...................... 55 Incident ....................... 65 Index ......................108 Installation....................65 Installation instructions ..................
  • Page 110 EQJW145: Heating controller Index Return temperature ............28, 43, 49, 51, 68, 97 Room operating unit ................44, 68 Room sensor....................44 Room temperature ..................27 Room temperature connection .............. 27, 97 Room temperature recording............... 26 Rotary switch....................47 RS485 ......................42 Safety thermostat ..................

This manual is also suitable for:

Equitherm

Table of Contents