Install T-Op Ii Assembly Onto Apparatus Bushing - Eaton 600 A 15 kV class T-OP II Assembly/Installation Instructions

Deadbreak apparatus connectors
Table of Contents

Advertisement

Remove alignment segment by applying pressure to the
T-Wrench to separate the alignment segment from the
LRTP . Recycle the align ment segment.
See Figure 9 for illustration of completed
LRTP installation.
T-OP II ASSEMBLY
T-WRENCH
LRTP
Figure 9 . LRTP permanently installed into T-body
forming the T-OP II assembly

Install T-OP II assembly onto apparatus bushing

Step 8
Install stud into apparatus bushing
Ensure unit is de-energized.
Thread the shorter threaded end of the T-OP II stud
into the apparatus bushing until hand tight. (Refer to
Figure 10).
Engage the flats on the stud with a 1/2" wrench and
thread the stud into the bushing an additional 1/4
revolution past hand tight.
Remove any shavings that may have been raised during
the threading procedure.
SHORT THREADS
INTO BUSHING
APPARATUS BUSHING
Figure 10 . Line illustration of bushing stud installation
600 A 15/25 kV Class T-OP II connector assembly installation instructions
SEPARATED
ALIGNMENT
SEGMENT
EXTENDED
STUD (STUD-T)
Step 9
Install the T-OP II assembly on the apparatus bushing
Clean and lubricate mating interfaces of the apparatus
bushing and T-body with the lubricant supplied.
Push the T-OP II assembly onto the apparatus bushing
until the extended length stud makes contact with the
rotating nut in the LRTP .
Insert the 5/16" torque tool into the 200 A tap and
engage the rotating nut. (Refer to Figure 11.)
Place a screwdriver or the T-wrench through the hotstick
operating eye of the torque tool (live-line tools can be
used to operate the T-OP II when de-energized) and
tighten the T-OP II assembly until the tool ratchets.
(20-25 ft.-lbs.)
N
ote:
If 5/16" hex rod (HD625) is used with customer
supplied torque wrench, thighten to 20-25 ft.-lbs.
Remove torque tool.
T-OP II
TQHD625
ASSEMBLY
TORQUE TOOL
T-WRENCH
Figure 11 . Installing the T-OP II assembly onto the
apparatus bushing
Step 10
Cap the 200 a interface
Clean and lubricate 200 A interface of LRTP and mating
apparatus (i.e., protective cap, grounding elbow, M.O.V.E.
arrester) with lubricant supplied. (Refer to Figure 12.)
To cap interface, follow installation instructions supplied
with the separable insulated connector used.
INSTALLATION INSTRUCTIONS MN650048EN May 2017
600 A
INTERFACES
APPARATUS
BUSHING
4

Advertisement

Table of Contents
loading

This manual is also suitable for:

600 a 25 kv class t-op ii

Table of Contents