Download Print this page

Eaton Cooper Power Series Installation Instructions

Deadbreak connectors, insulated standoff bushing

Advertisement

Quick Links

Deadbreak Connectors
Catalog Data
CA650043EN
600 A 15 and 25 kV class PUSH-OP ™
insulated standoff bushing
Effective April 2015
Supersedes 600-25 August 2002
COOPER POWER
General
Eaton meets the full requirements of IEEE
Std 386™-2006 standard, Separable Insulated
Connector Systems with its Cooper Power™
series 600 A, 15 and 25 kV insulated PUSH-OP™
standoff bushing.
The bushing provides a single deadbreak interface
made of high quality insulating epoxy material.
It is used in switchgear, transformers, and
other apparatus to isolate and sec tion al ize an
energized cable. Temporary or permanent parking
of energized 600 A 15 and 25 kV PUSH-OP
deadbreak connectors is simplified with the use of
an insulated standoff bushing.
The PUSH-OP insulated standoff bushing is
de signed to be installed in the parking stand
mounted on a switchgear, transformer, or other
apparatus. A drain wire lug is pro vid ed on the
standoff bracket for at tach ment of a drain wire
lead to ensure deadfront construction. The bushing
provides a fully-shielded, submersible connection
for deadbreak operation.
All standoff bushing brackets have a stainless
steel eyebolt with a brass pressure foot. The
bushing body is bolted to a stainless steel base
bracket using a stainless steel bolt. The bracket
and latch mechanism provides easy installation
of a PUSH-OP connector without any threading
operations.
Installation
A clampstick tool is used to place the standoff
bushing in the parking stand on the front plate of
the apparatus. The PUSH-OP connector is then
installed onto the standoff bushing tap. Refer to
Service Information S600-65-1 600 A 15/25 and
35 kV Class PUSH-OP Insulated Standoff Bushing
Installation Instructions for complete installation
details.
Production tests
Tests are conducted in accordance with IEEE Std
386™-2006 standard.
ac 60 Hz 1 Minute Withstand
40 kV
Minimum Corona Voltage Level
19 kV
Tests are conducted in accordance with Eaton
requirements.
Physical Inspection
Periodic Dissection
Periodic Fluoroscopic Analysis
SERIES

Advertisement

loading

Summary of Contents for Eaton Cooper Power Series

  • Page 1 600 A 15 and 25 kV class PUSH-OP ™ insulated standoff bushing General Eaton meets the full requirements of IEEE Std 386™-2006 standard, Separable Insulated Connector Systems with its Cooper Power™ series 600 A, 15 and 25 kV insulated PUSH-OP™...
  • Page 2 15 Minute Withstand WALL BIL and Full Wave Crest Minimum Corona Voltage Level Voltage ratings and characteristics are in accordance with IEEE Std 386™-2006 standard. 15/25 kV S7 0.75" (19 mm) S8 5.14" (130.6 mm) Figure 2. PUSH-OP stacking dimensions. www.eaton.com/cooperpowerseries...
  • Page 3 Table 2. Standoff Bushing Kit Description Catalog Number Insulated Bushing PISB625 Insulated Standoff Bushing with Hitch Pin PISB625HP Each kit contains: Standoff Bushing with Bracket • Shipping Cap (not for energized operation) • Silicone Lubricant • Installation Instruction Sheet • www.eaton.com/cooperpowerseries...
  • Page 4 Eaton.com Eaton’s Cooper Power Systems Division Eaton, Cooper Power, and PUSH-OP are 2300 Badger Drive trademarks of Eaton in the U.S. and other Waukesha, WI 53188 countries. You are not permitted to use these United States trademarks without the prior witten consent Eaton.com/cooperpowerseries...

This manual is also suitable for:

600 a 25 kv class push-op600 a 15 kv class push-op