Download Print this page

Moxa Technologies ioLogik E1200 Series Quick Installation Manual page 2

Remote ethernet i/o with 2-port ethernet switch
Hide thumbs Also See for ioLogik E1200 Series:

Advertisement

Relay Output:
Type: Form A (N.O.) relay outputs, 5A
Contact Rating: 5 A @ 30 VDC, 5 A @ 250
VAC, 5 A @ 110 VAC
Inductance Load: 2 A
Resistance Load: 5 A
Breakdown Voltage: 500 VAC
Relay On/Off Time: 10 ms, 5 ms (Max.)
Initial Insulation Resistance: 1G min. @
500 VDC
Expected Life: 100,000 times (Typical)
Initial Contact Resistance: 30 milli-ohms
(Max.)
Pulse Output: 0.3 Hz at rated load
Analog Input:
Type: differential input
Resolution: 16 bits
I/O Mode: Voltage / Current
Input Range: 0 to 10 VDC, 4 to 20 mA
Accuracy:
• ±0.1% FSR @ 25°C
• ±0.3% FSR @ -10 and 60°C
Sampling Rate (all channels): 12 samples
per second
Input Impedance: 10M ohms (min.)
Built-in Resistor for Current Input: 120
ohms
Installation
Power and Networking
Connect the +12 to +36 VDC power line to the
ioLogik E1200's terminal block V+; connect the
ground from the power supply to the V-. Connect
the ground pin (
) if earth ground is available
Power Supply
+24VDC Nominal
(+12 to 36VDC)
For safety reasons, the wires attached to
Note:
the power should be at least 2 mm in
diameter.
ioLogik E1200 Series Quick Installation Guide
Jumper Settings
The ioLogik E1212 and E1240 require configuring
the jumpers inside the enclosure. Remove the screw
on the back panel and open the cover to configure
the jumpers.
For the ioLogik E1212, DIO mode configuration is
as follows: (default: DO Mode)
For the ioLogik E1240, analog mode configuration
is as follows: (default: Voltage Mode)
Mounting
The ioLogik E1200 is designed with a vertical form
factor, and can be used with both DIN-Rail and
Wall Mounting. When mounting on a rail, release
the bottom mounting Kit, install the ioLogik on the
rail, and restore the bottom mounting kit to fix the
ioLogik on the rail. When wall mounting, release
the both upper and bottom DIN-Rail kit.
The ioLogik E1200 has two built-in Ethernet switch
ports for connecting either a standard direct or
cross-over Ethernet cable to either RJ45 port.
LED Indicators
Type
Color
Description
Amber System power is ON
Power
Off
System power is OFF
Green System is ready
Flashes every 1 sec when the
Flashing
"Locate" function is triggered
Flashes every 0.5 sec when the
Ready
Flashing
firmware is being upgraded
A cycle of on/off period: 0.5
Flashing
second shows "Safe Mode"
Off
System is not ready.
Green Ethernet connection enabled
Port 1
Flashing Transmitting or receiving data
Green Ethernet connection enabled
Port 2
Flashing Transmitting or receiving data
I/O Wiring
Digital Input
Digital Output (Sink Type)
Relay Output (Form A)
Analog Input
ioLogik E1200 Series Quick Installation Guide

Advertisement