12.10

Toolbar: Security

The UPS initializes in the USR, or lowest security mode. To change the display security level, press the
Security button.
The screen displays an alpha/numeric keypad to enter the appropriate password for the desired security
level. The UPS ships with a default ADM password of ADMIN.
In the example below, to change the security level from USR to ADM:
1.
Press the Security button. The alpha/numeric keypad is displayed.
2.
Type in the ADM password "ADMIN" – Press the ABC button once for A, twice rapidly for B, etc.
3.
After entering the password, press WRITE.
4.
If the password is accepted the display will show "Successful". Press QUIT to return to the Main
display, and the Security button will display the ADM security level.
If the password is not accepted, you can retry submitting the password as many time as desired.
Press QUIT to exit the Change Password without changing the password and return to the main
screed.
5000
2014012345
5CP0G020KWWK 20KVA
4400F3F300FAB 30KVA
Welcome to 5000 Series UPS...
12.11

Toolbar: Buzzer ON/OFF

The UPS Buzzer sounds when a fault occurs or when the UPS switched to backup mode. The Toolbar
allows the user to turn on/off the buzzer.
The buzzer can also be enabled or disabled through the setup menu. If the Buzzer is disabled through
the setup menu, the Toolbar Buzzer button will be disabled.
12.12

Toolbar: Touch ON/OFF

The touchscreen can be turned OFF (locked) by pressing the TOUCH ON/OFF button. With TOUCH
OFF, only the TOUCH button is active, the rest of the display will not respond to touch.
56
FIGURE 12.8: CHANGING SECURITY LEVEL
5000 Series NEMA-3R 3-Phase UPS Installation and Operation Manual – 92975-000